background image

10 

 

requirement 

Individual load current 

Full-scale: 10A/ 16A, Accuracy:±1%+0.1, 
resolution:100mA, Response:400ms 

Temperature/humi
dity 
Technology 
requirement 

Temperature 

Accuracy:±1

Response: 400ms 

Humidity 

Accuracy:±5%RH,  Response: 400ms 

Product size 

Product size

L×W×H

 

X

2

×56×52mm 

Mounting hole 

X

3

 

Case color 

Color 

Black 

Fittings 

Installation bracket 

1 set 

Network connection 
cable 

2M blue network cable*1 

Daisy-chain connection 
cable 

2M yellow network cable*1 

Serial connection cable 

2M Ivory Serial cable*1 

User manual 

1 set (CD) 

10 

Optional fittings 

Sensor   

Temperature/humidity sensor 

Smoke sensor 

Door sensor 

Water logging sensor 

11 

Environment 

Working Environment 

Temperature: 0

+45

   

Relative humidity: 30%

90% 

Storage Environment 

Temperature: -20

+70

 

Relative humidity :0%

95% 

12 

ROHS 

Compliance 

 

This is a Class A product. In home environment, this product may cause radio interference.   
In this case, the user may be required to take appropriate measures. 
Hereby Assmann Electronic GmbH, declares that the Declaration of Conformity is part of the shipping content.   
If the Declaration of Conformity is missing, you can request it by post under the below mentioned   
manufacturer address. 

 

www.assmann.com 

Assmann Electronic GmbH 
Auf dem Schüffel 3 
58513 Lüdenscheid 
Germany 

 

 

Summary of Contents for DN-95624

Page 1: ...Smart Power Distribution Unit QIG DN 95624 DN 95625 DN 95628 DN 95632 DN 95634 DN 95640 DN 95641 DN 95642 DN 95643 ...

Page 2: ...hock when you cannot verify grounding Reconnect the PDU to the power outlet only after you make all connections Operation under unfavorable environmental conditions must be avoided Humidity over 80 relative wet ambient temperatures above 50 C solvents flammable gases dust vapors If external damage to this PDU is detected do not operate this PDU Take this PDU immediately out of service if external ...

Page 3: ...tor 10 RESET button 11 USB port for WIFI access or software upgrade 12 NET 10 100M Ethernet communication port 13 SER Serial communication port support MODBUS 14 IN for daisy chain 15 OUT for daisy chain 16 T H1 temperature and humidity sensor port 1 17 T H1 temperature and humidity sensor port 2 18 SENSOR extend sensor hub communication port sensor hub support 2 temperature humidity sensor 2 door...

Page 4: ... 95624 DN 95625 DN 95640 DN 95641 DN 95642 B series DN 95628 D series DN 95632 DN 95634 DN 95643 2 Hardware Introduction 2 1 System initialization The buzzer sounds when the SMART PDU is switched on and it stops after 3 seconds Then the LCD screen is lighted after 6 seconds with the following information displayed Vertical 0U Horizontal 1U Note 192 168 1 163 is the default IP address and this is t...

Page 5: ...e part number CPU ARM926EJ S means the type of the device CPU chip Version 1 0 0 is the software version number M S Master means the Master Unit and Slave 1 means the Slave unit 1 1 4 means the order of Slave unit Type 3 phase C means the device is 3 phase C series one Through the DOWN or UP key to scroll down or up to the next previous page turn to the main menu and select the second item Total t...

Page 6: ...n to the main menu and then press DOWN key to select Temp Hum to view the temperature humidity as below Press ENTER to return to the main menu and then press DOWN key to select Sensors to view the door water logging and smoke sensor status as below Press ENTER to return to the main menu then press DOWN key to select Output to view each individual outlet current as below U 214V I 00 0A P 0 000kW E ...

Page 7: ...vides a lot of network services like WEB server SNMP Telnet SMTP and NTP It s easy to do second development and software integration 3 2 Access method Web based can access via browsers like Internet Explorer Google Chrome and Fire fox supports WIFI including the mobile device like smart phone and tablet SNMP v1 v2c v3 Telnet and Serial console like MODBUS 3 2 1 Web access Open a browser and enter ...

Page 8: ...logo and function menus and language selector Device information display device name device series and device status and function level Output status display output name on off state individual current individual power power factor and environment status From the drop down menu of device to check the information of Slaves More detailed information on operating and configuring the device can be fou...

Page 9: ...31 24way D Series DN 95632 24way DN 95633 16way DN 95634 24way Output voltage 110 220VAC 50 60 Hz Output current 16A 32A 3 Control ports Net port 1 RJ45 port Daisy chain port 2 RJ45 port Software update port 1 RJ45 port Temperature humidity port Max 2 RJ11 port can add more Smoke sensor port Max 1 RJ11 port optional Water sensor port Max 1 RJ11 port optional Door sensor port Max 1 RJ11 port option...

Page 10: ...CD 10 Optional fittings Sensor Temperature humidity sensor Smoke sensor Door sensor Water logging sensor 11 Environment Working Environment Temperature 0 45 Relative humidity 30 90 Storage Environment Temperature 20 70 Relative humidity 0 95 12 ROHS Compliance This is a Class A product In home environment this product may cause radio interference In this case the user may be required to take appro...