11
2.
If positive gap is bigger than 20 m or connecting pipe is longer than
30 m. Extension component is needed.
3.
Install oil bending in every 6 m vertical height of gas pipe when the
installation vertical height is over 10 m.
4.
Liquid pipe shall not be under the sunlight directly. Heat insulation is
needed.
5.
The gas pipe and condensate drain of indoor unit shall piping with
particular angel (exhaust pipe angle ≥
0.3°).
6.
When installed in negative gap, condenser liquid pipe shall piping
with particular angel (gas pipe angle ≥
0.3°)
Figure 3-1 Rack mounted cooling positive and negative installation instruction
Floor
Heat shield
Condensate drain(incline)
Liquid & Gas pipe
(Heat insulation)
Gas pipe
(incline)
Outdoor
unit
Indoor
unit
Oil
bending
AC
Gas pipe
(incline)
Floor
Heat shield
Liquid & Gas pipe
(Heat insulation)
Condensate drain(incline)
Outdoor
unit
Indoor
unit
AC