OPU-1
UNIVERSAL POWER-LINE CARRIER SYSTEM TYPE OPU-1
GENERAL DESCRIPTION - Rev 7 (May 2019)
61/67
The rest of the terminals
Terminals that do not have disconnect
devices and that are suitable for conductors of
up to 1.31 mm
2
of section
In disturbed environments it is recommended to use screened cables for the
connections. For safety reasons the screen of the connection cables must be grounded,
the connection to earth being made at just one end to avoid interference.
5.10
MANAGEMENT SYSTEM
Terminal management interface
10/100Base-TX LAN interface
Type of interface
IEEE 802.3 (CSMA/CD)
Connector
8-pin RJ-45 female
Type of cable
UTP-5
Transmission rate
10 or 100 Mbit/s
OPU-1 Management System
Programming and monitoring of the system
from a PC running a standard Web browser,
without the need for additional software.
❖
Programming:
network
parameters,
terminal identification and configuration,
transmission and reception frequency
bands, audio-frequency input and output
levels, signal-level percentages for each
service in normal operation or boosting
condition, digital modulation scheme (QAM
or OFDM/OQAM), gross bit rate of the
QAM digital modem, digital ports, fall back/
increase rate, optional analog modules,
external signalling relays, clock and
synchronisms and loops.
❖
Monitoring: Chronological list of alarms and
events, terminal alarms, receive pilot level,
S/N ratio, Quality of the link (established
with regard to Recommendation G.821),
and state of the digital ports.