background image

www.glendimplex.de

DOK4x HOIAO FxDEN · FD 0001

19

Air-to-water heat pump M Flex

English

6.8 Refrigerant pipe connections

!!

ATTENTION!

Work on the system must only be performed by authorised
and qualified after-sales service technicians.

Certain requirements with regard to pipe length and rise must
be complied with when installing refrigerant pipes. Once all
conditions are met, the connection of the connecting pipe from
the outdoor unit to the indoor unit can begin.

6.8.1 Requirements for the pipe length

and rise

The indoor unit of the heat pump is already filled with refriger-
ant. The standard pipe length is 3.0 m. Up to a length of 7 m, no
additional refrigerant filling is required. For pipe lengths over
7 m, the system must be filled with additional refrigerant in ac-
cordance with the table.

!!

ATTENTION!

Incorrect filling with refrigerant could lead to faults during op-
eration.

!!

ATTENTION!

The length of the refrigerant line is calculated based on the
total line length from the respective connection point of the
indoor unit to the outdoor unit. 
Incorrect refrigerant filling or refrigerant lines over 10 m result
in a risk of faults during operation and a complete failure of
the heat pump.

*Example: When installing the 9 kW model at a distance of
10 m, 420 g refrigerant must be added according to the follow-
ing calculation: (10 - 7) x 140 g = 420 g

HINWEIS

ºº

º

ºº

º

NOTE

If the indoor unit is mounted 2.5 m or more metres higher or
lower than the outdoor unit, a cooling technology specialist
must perform a separate check to ensure that the devices for
conveying the oil up and down the pipes have been installed
correctly in the exhaust gas pipe. The maximum rise (B) be-
tween the indoor and outdoor units is 5 m.

HINWEIS

ºº

º

ºº

º

NOTE

The specified operating data of the device refers to the stand-
ard pipe length, see device information.

6.8.2 Pipe connection

The connection points for the refrigerant lines must be estab-
lished using the brazing process. All generally applicable instal-
lation and work steps must be followed for this. The reducing
sleeves provided must be used for connecting the outdoor unit
in the M Flex 0609 version.
During the brazing process, the pipe system must be flushed
with an inert gas (e.g. nitrogen). The adjacent components must
be suitably cooled to prevent them being damaged.

6.8.3 Leak test and evacuation

Air and moisture in the cooling system have unwanted effects
as outlined below.
1) The pressure in the system increases.
2) The operating current increases.
3) The cooling (or heating) output falls.
4) Moisture in the cooling circuit can freeze and block the

capillary tubes.

5) Water can cause corrosion on parts in the cooling

system.

This means that the connection pipes must be checked for
leaks and pumped empty to remove any moisture and non con-
densable gases from the system.

Step 1: Preparation

Ensure that every pipe (liquid and intake side) between the in-
door and outdoor unit is connected correctly. Ensure that both
maintenance valves on the liquid and intake of the indoor unit
are closed at this point.

Step 2: Leakage tightness test

Connect a dry nitrogen gas cylinder (with Schrader) on the
maintenance valve.

Apply 40 bar dry nitrogen to the system. Close the cylinder
valve once the test pressure is reached. The next step is to
search for leaks with liquid soap.

HINWEIS

ºº

º

ºº

º

NOTE

In order to prevent liquid nitrogen from entering the cooling
system, the top side of the gas cylinder must be higher than
the bottom side when pressure is building in the system.

All pipe connections (internal and external) must be
checked for leaks with liquid soap. Bubbles indicate a leak.
The soap must then be wiped away with a clean cloth.

If no leaks are found on the system, drain off the nitrogen.

Model

Pipe size (mm)

(external 

diameter x wall 

thickness)

Length A (m)

*additional

refrigerant

(g/m)

Gas

Liquid

Normal Min. Max.

M Flex 0609

12 x 1

10 x 1

7

3

10

75

M Flex 0916M

18 x 1

12 x 1

7

3

10

140

Outdoor unit

Indoor unit

A

B

Outdoor unit

Indoor unit

A

B

max. 5 m

max. 5 m

Summary of Contents for M Flex Air

Page 1: ...K4x HOIAO FxDEN EN FD 0001 M Flex 0609 M Flex 0916 M Flex 0916M Installation and Operating Instruction Air to water heat pump in integral design Glen Dimplex Deutschland Dimplex 09CHOIAOF6 16IHOIAOF6...

Page 2: ......

Page 3: ...tric wire 11 6 2 Condensate drain 11 6 3 Connection on heating side 11 6 4 Domestic hot water connection 12 6 5 Temperature sensor connection 13 6 6 Electrical connection 14 6 7 Hydraulic integration...

Page 4: ...2 DOK4x HOIAO FxDEN FD 0001 www glendimplex de English Air to water heat pump M Flex 15 Information on the use of data 33 16 Declaration of conformity 34...

Page 5: ...fur ther connection requirements stipulated by local utility compa nies must also be observed When connecting the heating system all country specific reg ulations must also be adhered to This unit ca...

Page 6: ...ls the air i e ex tracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is pumped to a higher temperature level by increas ing its pr...

Page 7: ...ulating pump 5 Switch box with heating controller 6 Electric additional heater 2 4 or 6 kW for higher domestic hot water temperatures and for heating support 7 Safety valve start to leak pressure 2 5...

Page 8: ...6 DOK4x HOIAO FxDEN FD 0001 www glendimplex de English Air to water heat pump M Flex 3 2 Outdoor unit 1 Evaporator 2 Fan 3 Expansion valve 4 Switch box 5 Connection for refrigerant line 1 2 4 3 5 5...

Page 9: ...ed directly underneath the pallet To lift from the pallet the indoor unit can be tilted back by up to 45 and lifted by the handles on the back at the top Tilting more than 45 is not permitted Once the...

Page 10: ...nglish Air to water heat pump M Flex After the final positioning at the installation location remove the transport fastening on the sprung floor of the compressor on both sides ATTENTION Before commis...

Page 11: ...tion site Cap 12 1 on page 26 The responsibility for the heat pump installation lies with the specialist system construction company During the installation local requirements such as building regula...

Page 12: ...refrigeration lines have been connected to the indoor unit The domestic hot water sensor pre installed on the indoor unit must be inserted in the designated immersion sleeve of the cyl inder Neither...

Page 13: ...ons of the countries in question must be observed 6 3 Connection on heating side Before connecting the heating system to the heat pump the heating system must be flushed to remove any impurities resi...

Page 14: ...ed with a suitable frost protection if heat pump systems are implemented in buildings where a power failure can not be detected holiday home 6 4 Domestic hot water connection Installation and commissi...

Page 15: ...ay that all weather conditions are taken into consideration and the meas ured value is not falsified Mount on the external wall on the north or north west side where possible Do not install in a shelt...

Page 16: ...N FD 0001 www glendimplex de English Air to water heat pump M Flex 6 6 Electrical connection 6 6 1 Electrical diagram integration example Symbol legend see cap 6 6 2 on page 15 Equipment marking see c...

Page 17: ...A451 Cooling active B3 Domestic hot water thermostat B4 Swimming pool water thermostat E10 1 Electric heater E10 2 3 Oil gas boiler H5 Remote fault indicator K21 Flange heater K22 Utility block K23 Di...

Page 18: ...t be connected on plug X1 1 230V IN white on the adapter board The supply cable L N PE 230 V 50 Hz must have a continuous voltage For this reason it should be tapped upstream from the util ity company...

Page 19: ...www glendimplex de DOK4x HOIAO FxDEN FD 0001 17 Air to water heat pump M Flex English 6 7 Hydraulic integration diagram 6 7 1 Hydraulic integration diagram integration example...

Page 20: ...p M Flex 6 7 2 Symbol legend Isolating valve Safety valve combination Circulating pump Room temperature controlled valve Isolating valve with check valve Heat consumer temperature sensor Check valve T...

Page 21: ...lines must be estab lished using the brazing process All generally applicable instal lation and work steps must be followed for this The reducing sleeves provided must be used for connecting the outdo...

Page 22: ...hed An absolute pressure of at least 0 2 mbar must be achieved during evacuation Pressures below 0 2 mbar are advisable however Close the vacuum pump and start filling immediately Step 4 Filling Once...

Page 23: ...Ensure that the condensate drain functions properly The outflow from the heating water pressure relief valve must also function correctly The system must be completely filled with refrigerant and the...

Page 24: ...ned by a heating technician Based on current information we recommend using a 5 phosphoric acid solution for cleaning purposes However if cleaning needs to be performed more frequently a 5 formic acid...

Page 25: ...from the power supply HINWEIS NOTE Personal protective equipment protective goggles safety shoes and gloves where necessary must be used when work ing on the device Components with plastic parts must...

Page 26: ...e of 10 m outdoors4 Normal operation reduced operation 3 dB A 25 x 24 25 x 24 25 x 24 3 5 Sound power level in accordance with EN 12102 at A7 W55 indoors dB A 45 45 45 3 6 Sound pressure level at a di...

Page 27: ...ystem according to EN 14511 For an analysis of the economic and energy efficiency of the system other parameters in particular the defrosting capacity the bivalence point and regulation should also be...

Page 28: ...m 0 5 m 0 5 m 460 39 710 40 790 850 1231 600 206 790 538 695 995 95 174 120 55 105 40 538 39 2 3 27 110 40 205 108 160 30 30 50 710 778 372 1 1 1 7 1 2 1 3 1 4 1 8 1 5 1 6 1 1 1 2 1 3 Air intake Direc...

Page 29: ...AO FxDEN FD 0001 27 Air to water heat pump M Flex English 12 2 Dimension drawing indoor unit 2 8 2 9 2 1 2 10 2 3 2 2 2 7 2 12 2 11 600 1400 544 722 750 113 125 95 0 117 187 490 560 840 910 980 1050 1...

Page 30: ...ugh refrigerant line 18 mm 1 6 Optional feedthrough electric wires 12 mm 1 7 Optional feedthrough electric wire 1 8 External dimensions wood design variant 2 Indoor unit 2 1 Outlet overpressure 2 2 Fe...

Page 31: ...55 dB m h Emissions of nitrogen oxides NOx mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If C...

Page 32: ...mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined by measurement nthen...

Page 33: ...mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined by measurement nthen...

Page 34: ...ered by the warranty If it was not possible to remedy the defect the manufacturer shall either deliver a replacement free of charge or issue a reimburse ment for the reduced value In cases in which re...

Page 35: ...t en cryption methods III Use of service providers Personal data required for maintenance purposes such as your address contact details and framework data on the contract is made available to after sa...

Page 36: ...DOK4x HOIAO FxDEN FD 0001 www glendimplex de English Air to water heat pump M Flex 16 Declaration of conformity You can find and download the current CE conformity declaration at https glendimplex de...

Page 37: ...www glendimplex de DOK4x HOIAO FxDEN FD 0001 35 Air to water heat pump M Flex English...

Page 38: ...36 DOK4x HOIAO FxDEN FD 0001 www glendimplex de English Air to water heat pump M Flex...

Page 39: ...www glendimplex de DOK4x HOIAO FxDEN FD 0001 37 Air to water heat pump M Flex English...

Page 40: ...glendimplex de www glendimplex de Gesch ftsstelle sterreich Glen Dimplex Austria GmbH Hauptstra e 71 A 5302 Henndorf am Wallersee T 43 6214 20330 F 43 6214 203304 info dimplex at www dimplex at Offic...

Reviews: