Function description: DNDS 1C, 1D, 1FA & 1GA 

DNDS 1C

1D

1FA

 & 

1GA:  

The DNDS acts as a failsafe monitor of a rotary respectively linear motion and standstill. The speed monitor shut-
down trigger point can be programmed via 4 inputs (D1–D4). This shutdown trigger point can be further modified 
from 100% down to 5 % via the 4inputs (F1–F4) 

DNDS 1C, 1D

 has an internal (R) input to switch between constant and variable creep velocity (see table 1 and 2). 

The motion detection can be monitored via 2 PNP-proximity sensors or a rotary encoder.  
If PNP-proximity sensors are used, attention must be paid to mount them in a way, so always one of the two sen-
sors is activated. 
Rotary encoders can only be connected using a DNIA adaptor (for the rotary encoder specifications, see the DNIA 
operating instructions).  

DNDS 1FA

1GA

 has an external (R) input to switch between constant and variable creep velocity. A further exter-

nal (SH) input is used for switching over between creep velocity and standstill (see table 1 and 2).  
For motion monitoring a rotary encoder is required. The Rotary encoder is connected via a DNDA 15/8 or DNDA 
25/8 adaptor to the DNDS 1FA, 1GA 

 
Function of the inputs of DNDS 1C, 1D, 1FA & 1GA 

D-inputs

Setting the automatic operation mode speed in 16 steps (00-15 = 100 – 800 Hz, table 1) 

D-inputs are only of importance if at least one F-input is connected to 24V 

If the F-inputs are not active (open) and the R-input is active, the active D-inputs determine the value of the tool 
setting speed. 

F-inputs: 

F-inputs reduce the stting value via the D-inputs in 15 steps, 01-15 = 25-100%. 

The F-inputs are also a switch over between tool setting (all F= open) and automatic operation mode (any F con-
nected with 24V). The tool setting speed is variable between 1-20 Hz or constant 5 Hz. 

The F-inputs setting is store internally to determine the tool setting speed, if all F inputs are switched off. The 
stored F setting is valid until the equipment is powered off.  

The value of the tool setting speed is determined by the stored F-inputs, if the D-inputs are open and the R-input 
is active. 

R-input: 

R-input works only if the F-inputs are switched off (open). 

If the R- and D-inputs are active the creep rate is determined by the active D-inputs. (see Table 1)  

If the  D-inputs are open the tool setting speed is determined by the stored F setting . 

If the R-input and the Finputs are not active, the standstill is monitored. 

R- and SH inputs must not be connected to 24V at the same time.

 

SH-input: DNDS 1FA, 1GA only 

The SH input is used to switch between tool setting speed and standstill (50Hz and 5Hz) 

The SH-input works only if the R-input and all F-inputs are switched off (open). 

If the SH-input and the F-inputs are open the standstill will be monitored. 

If the SH-input is active (SH connected to 24V) and the F-inputs are open the tool setting speed will be moni-
tored. 

 

 
 

Summary of Contents for DNDS 1C

Page 1: ...DNDS Kompakt Original Instruction manual Only for replacement requirements Safety for men and machines...

Page 2: ...les for testing and certification of safety switch devices DIN EN 60947 5 1 Low voltage switch gear and control gear electromechanical control circuit devices DIN EN ISO 13849 1 Safety related parts o...

Page 3: ...NA Elektronik GmbH Esslinger Stra e 84 72649 Wolfschlugen Tel 07022 9517 0 Fax 07022 95 17 51 www dinaelektronik de info dinaelektronik de Quality management system DQS Certificate DIN EN ISO 9001 200...

Page 4: ...monitoring 8 Function description DNDS 1C 1D 1FA 1GA 9 Function of the inputs of DNDS 1C 1D 1FA 1GA 9 Machine speed setting with DNDS 1C 1D 10 Machine speed setting with DNDS 1FA 1GA 10 Function modes...

Page 5: ...PLe Type test certificate No ET 08151 BG Test certificate No ET 08152 Certification base 2004 108 EC EMC directive EN55011 A1 EN61000 6 2 GS ET 20 basic principles for testing and certification of saf...

Page 6: ...mity sensors or an encoder via a DNIA adaptor DNDS 1FA DNDS 1GA 2GA The encoder is connected via a DNDA Cable adaptor type DNDA Status indicators Programmable machine rpm setting The DNDS complies wit...

Page 7: ...r Me system DNDS 1C 1FA 2C 2FA Applications of the outputs STOP contacts Standstill monitoring If the protection cover is closed and one or more drives are in movement the NO contacts 13 14 open immed...

Page 8: ...tandstill as well as the adjusted speed of the function mode the NO contacts 23 34 and 43 44 open immediately The LED SPEED does not illuminated The drives will be stopped by emergency stop circuit ST...

Page 9: ...z table 1 D inputs are only of importance if at least one F input is connected to 24V If the F inputs are not active open and the R input is active the active D inputs determine the value of the tool...

Page 10: ...achine speed setting with DNDS 1FA 1GA connected to24 VDC NC open T1 Automatic mode speed setting mode 1 T2 Reduction in for each position of D in T1 mode 1 Programmable F F NC Programmable D D F NC i...

Page 11: ...ent by using a DNDA 15 8 or DNDA 25 8 adapter cable to the encoder Please note for operation To prevent a welding together of the contacts a fuse 6 A slow acting must be connected before the output co...

Page 12: ...lse diagram Function of the inputs of DNDS2 C 2D D inputs Position 0 7 T1 DNDS 2C 2D Position 0 15 T2 DNDS 2GA The D inputs are a switch over between tool setting D open and automatic operation mode D...

Page 13: ...cables to the encoder Please note for operation To prevent a welding together of the contacts a fuse 6 A slow acting must be connected before the output contacts The total of the reaction times must n...

Page 14: ...virumental temperture Mechanical life cycles 5 x 10 7 Electrical life cycles DNDS 1C 1FA 2C AC 230V 5A cos 1 DNDS 1D 1GA 2D 2GA AC 230V 6A cos 1 3 x 10 5 1 x 10 5 Sum of currents for all contacts 16A...

Page 15: ...ction 2 tracks 90 out of phase 2 signals per track that are 180 out of phase The signals of encoder are not allowed to be generate synthetically Encoder signals TTL or Sinus Cosinus 1 1 A A B B Sin Si...

Page 16: ...Connected with DNDS 2D or DNDS 2C DNIA DNDA 15 IA1 IA1 A1 A1 IA2 IA2 24VDC Surveillance A1 A2 IN2 13 14 23 24 33 34 43 44 IN1 berwachung Monitoring 1 2 D1 D2 D3 IN4 IN3 D4 D5 D6 A1 A1 IA1 IA1 IA2 IA2...

Page 17: ...Instruction manual DNDS Kompakt Products safety technique DNDS KOMPAKT Version 04 2011 03 16 page 17 from 20 Certificate...

Page 18: ...Instruction manual DNDS Kompakt Products safety technique DNDS KOMPAKT Version 04 2011 03 16 page 18 from 20...

Page 19: ...Instruction manual DNDS Kompakt Products safety technique DNDS KOMPAKT Version 04 2011 03 16 page 19 from 20...

Page 20: ......

Reviews: