Hardware Manual
SAFEONE DNSR-2R Time Delay Relay
19
7
Technical data
7.4
Contact outputs
Outputs
37/38, 47/48
14,24
Contact material
AgNi
Output guidance
Minimum switching current
see Contact service life section
10 mA
3 mA
Maximum switching current
* construction-related limitation
6 A*
1 A
0.5 A
Switching capacity in accordance
with IEC 60947-5-1
DC13:
2 A/24 V
DC13
at 0.1 Hz: 4 A/24 V
AC15:
3 A/250 V
Mechanical service life
≥ 10
7
switching cycles
≥ 5 x 10
7
switching cycles
Contact fuse
5 A gL/gG
Typical response/release time
10 ms/6 ms
7.5
General data
Type of protection (housing and terminals)
IP 20
Type of protection (place of installation)
Min. IP 54
Clearance and creepage distances
between circuits
in accordance with DIN EN 50178
Rated insulation voltage
37/38, 47/48
250 V AC
14,24
30 V AC
Rated surge voltage/insulation
4 kV
Degree of contamination
2
Overvoltage category
III
Housing material
Polyamide (PA), not reinforced