Product information
Products: safety technology
SafeLine
redaction 11 date 10.04.09 page 8 from 48
2. layer: Parameter mask
Selection timer(TC)
Central module parameter mask
Inputs, terminal
: labelling of inputs I1 to I20
SK1 I1..I3, SK2 I4..I6, Restart
:
SK
*
-Restart „
manually
“
by activating
Q
or „
Auto.
“ automatically
SLOK SK1, SLOK SK2:
the function SLOK SK1 and
SLOK SK2 is only important, if:
1. SK1 I1..I3 or SK2 I4..I6 as Emergency stop safety
circuit is used.
2. an external sensor or internal SafeLine error is
existed.
After SafeLine forces an emergency stop function like
the actuating of the emergency-stop button.
The forced emergency stop stopped the plant.
SafeLine works normally till the end of the SLOK Delay
time. After all outputs of SafeLine will be turned off.
The SLOK Delay time has to be selected such so long,
that the plant will be stopped safety.
2K_OFF
: If it is activated and Restart AUTO is se-
lected, no switch off/on of the circuit contact is neces-
sary for test after power off/on. By Restart MAN a quit
signal is necessary.
If 2K_OFF is not activated a switch off/on of the contact is necessary after power off/on. By Restart MAN a quit
signal is necessary.
SK Activation
: Safety circuit via static or clock signal (cross-circuiting detection)
Name 1
: Labelling of the inputs
BAWS
: Operation mode 3 or 6 switch positions via 3 or 6 inputs
O1
:
SLOK
: Output of operating state,
T8
: semiconductor output
FrqIn
: frequency input for motion control only possible with DNSL-ZMT, ZMB, ZMR and field bus module
Test O1..O7
: The internal check of the outputs O1, O2 till O5 and O6, O7 can be turned off and on.
The function „check turned off“ the outputs will not tested.
This feature is possible for all semiconductor outputs at all central modules.
TC, A. Relay, LA
: Change between time delay relays, auxiliary relays and logic modules. See below.
Timers, ZW-Anzug
: selection 3 or 6 on-delayed timers
Timers, Stepping
: „100ms“ time domain 100ms to 999,9s
„10ms“time domain 10ms to 99,9s
Off-delayed, on-delayed
:
Fields left
: Entry of time value, 10 = 1s with selection 100ms, 10 = 100ms with selection 10ms
Fields right
: Entry of the name of time delay.
Terminals O2 to O7
: fields for entry the name of the outputs.
DNCO Table
: If this function will be selected, a mask with two tables for frequency values will be appear. Every
table includes fields for 48 values. The frequency values assign the motions, that have be monitored.
See DNSL-DS.
DNCO Terminals
: The number of the monitored motions defines the necessary inputs at the central module or
DNSL-DS. Eight motions need 3 inputs, 16 motions need four inputs and 48 motions need 6 inputs.
IF1
: With the selection „ON” the function of a pulse generator (Takt Generator) is possible via the virtual contact
IF1. IF1 can be used to control an hardware output.
Takt Generator(100ms)
: The time of the signal „High“ and the signal „Low“ can be defined. The stepping is
100ms. 1 = 100ms, 10 = 1s etc.
SLOK Delay [s]
: If there is a defect in SafeLine or in the sensor system of SafeLine the output 01 will be turn off.
After an adjustable delay time 0 to 25s all outputs at SafeLine will be turn off. For the time length please take care
for the function SLOK SK1 or SLOK SK2
DS1, DS2
: With the central module there are two motion and standstill controls for two drives possible.
The sensors for the motion and standstill controls can be proximity switches. For a motion control there are two
proximity switches with 24V signals necessary. With the selection is this function available.
The input IN11 to IN14 are used for this function at the central module DNSL-ZMB, ZMT and ZMR.
Motion monitoring freq. [Hz];
SS1, SS2
: Entry the frequency value for standstill
F11, F21
: Entry the frequency value for tool setting mode
F12, F22
: Entry the frequency value for semiautomatic mode
F13, F23
: Entry the frequency value for automatic mode
: save and close.
: close without saving.