10
©
Dinel, s.r.o. CLM–36
ROPE ELECTRODE WITH ANCHOR
CLM-36_-31
E
- the length of electrode [mm]
c
- the distance from the centre line of
the silo - has to be as minimal as possible
t
- the length of the conduction rod -
approx. 500 mm
p
- the length of the press spring -
approx. 200 mm
steel anchor welding cylinder
(mat. 11375) or
dust-tight bushing
to be welded into the conical
bottom wall
AGGRESSIVE LIQUIDS, NON-METALLIC VESSELS
CLM-36N_-40
E – The length of electrodes
the lower end of the electrodes
have to be dipped min. 20 mm
below the lowest measured level.
h – The distance from the bottom
min. 30 mm
a – The distance from the wall
(min. ca. E/20)
Fig. 7: Installation of rope electrode with anchor
Fig. 8: Installation of level meter with reference electrode
For correct function of level type CLM-36N_-40 is necessary to ensure the impedance between
of the measured medium and ground. This can be provided by:
1) The medium is isolated from all devices that may cause temporary grounding of the medium
(pumps, valves, connection with the grounded tank by flowing medium).
2) If the first option is not possible, it is necessary to ground the medium permanently.