Start-Up/Commissioning 

DA-020S024QXxxx 
Spring Return, Modulating Control, 24 Vac/dc 

1.  Check Operation: 

a) 

Connect  wires  1  (red)  and  2  (black)  to  the  24  Vac/dc 
power supply. 

NOTE:   

With  no  input  signal  present,  the  DA-

020S024QXXXP  actuator  with  input  signal  inversion 
switch  set  to  Inverse  Acting,  will  start  driving  towards 
90°. 

b) 

Use  a  Digital  Multimeter  (DDM)  and  set  the  dial  to  Vdc 
for the actuator input signal.  

c) 

Connect wires 2 (black) and 8 (gray) to the DMM. 

d) 

Apply to input signal wire 8 (gray): 

Y  =  10  Vdc  (DA-020S024QXXXP  with  input  signal 
inversion switch set to Direct Acting). 

Y  =  2  Vdc  (DA-020S024QXXXP  with  input  signal 
inversion switch set to Inverse Acting). 

Allow the actuator shaft coupling to rotate from 0° to 90°. 

e) 

Apply to input signal wire 8 (gray): 

Y  =  2  Vdc  (DA-020S024QXXXP  with  input  signal 
inversion switch set to Direct Acting). 

Y  =  10  Vdc  (DA-020S024QXXXP  with  input  signal 
inversion switch set to Inverse Acting). 

The shaft coupling returns to the "0" position. 
 

DA-020S024DXxxx 
Spring Return, 2-Position, 24 Vac/dc 

2.  Check Operation: 

a) 

Connect wires 1 (red) and 2 (black) to 24 Vac/dc power 
supply.    Allow  the  actuator  shaft  coupling  to  rotate  from 
0° to 90°. 

b) 

Disconnect  wire  1  (red)  and  the  actuator  shaft  coupling 
returns to the "0" position. 

3.  Check Spring Return: 

a) 

Connect  wire  1  (red).    Allow  the  actuator  shaft  coupling 
to rotate halfway. 

b) 

Disconnect wire 1 (red).  The spring returns the actuator 
shaft coupling to the fail-safe "0" position. 

DA-020S024FXxxx 
Spring Return, Floating, 24 Vac/dc 

1.  Check Operation: 

a) 

Connect  wires  1  (red)  and  2  (black)  to  a  24  Vac/dc 
power supply. 

b) 

Apply  a  control  signal  (24  Vac/dc)  to  wire  6  (violet).  
Allow the actuator shaft coupling to rotate from 0 to 90°. 

c) 

Stop the control signal to wire 6 (violet). 

d) 

Apply a control signal (24 Vac/dc) to wire 7 (orange). 

Allow the actuator shaft coupling to rotate from 90° to 0°. 

2.  Check Spring Return: 

a) 

Apply  a  control  signal  (24  Vac/dc)  to  wire  6  (violet).  
Allow the actuator shaft coupling to rotate half way. 

b) 

Disconnect wire 1 (red).  The spring returns the actuator 
shaft coupling to the fail-safe "0" position. 

c) 

Connect wire 1 (red).  The actuator shaft coupling begins 
to move. 

DA-020S120DXxxx 
Two-Position, 120 Vac 

1.  Check Operation:  

a) 

Switch on 120 Vac power. 

b) 

Allow the actuator shaft coupling to rotate from 0 to 90°. 

2.  Switch off power.  The actuator shaft coupling will return to the "0" 

position. 

3.  Check Spring Return:   

a) 

Switch on 120 Vac power. 

b) 

Allow the actuator shaft coupling to rotate halfway. 

c) 

Switch  off  120  Vac  power.    The  spring  returns  the 
actuator shaft coupling to the fail "0" position. 

Troubleshooting 

 

To  avoid  injury  or  loss  of  life,  pay  attention  to  any 
hazardous  voltage  (for  example,  120  Vac)  when 
performing checks. 
 

Check that the wires are connected correctly. 

Check that DIP switch is set correctly, if used. 

Use  a  Digital  Multimeter  (DMM)  to  verify  that  the  operating 
voltage is within range. 

If the actuator is not working, check the damper for blockage. 

If  blocked,  remove  the  obstacle and  cycle  the  actuator  power  off 
and on. The actuator should resume normal operating mode. 

 

 

Summary of Contents for DA-020S Series

Page 1: ...eas where corroding deteriorating or explosive vapors fumes or gases may be present Ensure that all equipment is installed according to local regional and national regulations Personal injury or loss...

Page 2: ...not open the actuator If the actuator is inoperative replace the unit The shaft adapter can be mounted on either side of the actuator The actuator mounting orientation and shaft length determine how...

Page 3: ...the cables in water Device of protection class II protective insulation Device of protection class III protective insulation DA 020S024DXxxx 2 Position 24 Vac dc Class III DA 020S024FXxxx Floating 24...

Page 4: ...control signal Direct acting Factory setting Input signal 2 Vdc fail safe position Inverse acting Input signal 10 Vdc fail safe position Feedback Signal Inversion Allows inverting the position feedbac...

Page 5: ...fe 0 position DA 020S024FXxxx Spring Return Floating 24 Vac dc 1 Check Operation a Connect wires 1 red and 2 black to a 24 Vac dc power supply b Apply a control signal 24 Vac dc to wire 6 violet Allow...

Page 6: ...eries Siemens GQD Series Belimo TF Series Honeywell MS7503 Series Johnson M9203 Series Color Number Color Number Color Number Terminal Only Number Color Number Supply 24V Red 1 Red 1 Red 2 1 Red 2 Com...

Page 7: ...Dimensions Figure 10 Actuator and Mounting Bracket for models DA 020S024DXXXP FXXXP QXXXP Figure 11 DA 020S120DXXXX Actuator Only Figure 12 Actuators with Conduit Adapter for DA 020S024DX2XP FX2XP QX...

Page 8: ...g the correct wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change delete or add to the information in this manual at any...

Reviews: