102
Network Guide
5.
Press the down button
once to enter the
GEN CFG
submenu.
6.
Press the
Menu
button
several times until
BAUD RATE
appears on the display. The
current controller's baud rate is shown.
7.
Use the up and down buttons to set the controller's baud rate.
AUTO
detects and uses the
baud rate currently being used by the BACnet MS/TP network.
8.
Press the
Menu
button
once to apply the value.
9.
Press and hold the
Menu
button
for 5 seconds to exit the configuration menu.
Connecting to the LAN through an Allure EC-Smart-Vue Sen-
sor
The Cat 5e Cable subnetwork data bus extends the LAN to the Allure EC-Smart-Vue sensor to
provide convenient network access for maintenance and troubleshooting purposes.
The next sections explain how to bring to the L
ON
W
ORKS
network and BACnet network to the
Allure EC-Smart-Vue sensor. Both are handled slightly differently since there can only be a
limited number of enabled controllers on a L
ON
W
ORKS
network, whereas BACnet has no lim-
itations.
OR
Screen Timeout: 30 seconds
OR
Screen Timeout: 30 seconds