DTK-TSS1 

Total Surge Solution

User Guide 

DITEK CORPORATION

One DITEK Center

1720 Starkey Road

  Largo, Fl 33771

DTK-2MHTP (2-Pair Modular Hybrid Telco Protector)

Note: Connect this device in series between the field wiring and the 

alarm panel supply wiring.

1. Connect the communication loop circuit from the field to the side marked 

    UNPROTECTED. The first pair is connected to the terminals marked 1+ and 

    1- . If a second pair is used, connect to the terminals marked 2+ and 2-  . 

2. Connect the communication loop for the alarm panel supply wiring to the side 

    marked PROTECTED. 

DTK-2MHLPXXB (2-Pair Modular Hybrid Line Protector)

Note: Connect this device in series between the field wiring and the 

alarm panel supply wiring.

1. Connect the IDC (Initiating) wiring from the field to the side marked INPUT. 

    The first pair is connected to the terminals marked 1+ and 1- . If a second pair is 

    used, connect to the terminals marked 2+ and 2-  . 

2. Connect the IDC for the alarm panel supply wiring to the side marked OUTPUT. 

3. Connect the NAC (Notifying) wiring from the field to the side marked INPUT. 

    The first pair is connected to the terminals marked 1+ and 1- . If a second pair is 

    used, connect to the terminals marked 2+ and 2-  . 

4. Connect the NAC  for the alarm panel supply wiring to the side marked OUTPUT.

Repeat for the SLC (Signaling) circuit.

Note:

 There are up to 4 modules available for protection of any combination of IDC 

(Initiating), NAC (Notifying), or SLC (Signaling) circuits. Each module will protect 2 

pairs or circuits.

Note:

 All modules have been factory pre-wired for ground.  It is not necessary to

make any additional ground connections.

After all connections have been made and no hazards exist, restore power

DITEK CORPORATION

One DITEK Center 1720 Starkey Road Largo, Fl 33771

       1-800-753-2345         www.ditekcorp.com

Sales: 1-800-753-2345

Technical Support: 1-888-472-6100

191519 INT-100099-001 Rev 5

FIELD PAIRS

TO EQUIPMENT. 3' MINIMUM

DTK - 2MHLP

DITEK

MADE IN THE USA

DTK - 2MHTP

A

B

5

12

24

36

48

75

130

MODULAR SURGE PROTECTION        

VOICE - DATA- SIGNAL

UNPROTECTED

PROTECTED

1+

 1-

  2

+ 2

-

1+

 1-

  2

+ 2

-

Reviews: