           DITEK TSS1 

  (Total Surge Solution)

System Overview
TSS1 (Total Surge Solution)

The TSS1 is an integrated surge protection solution for alarm panels. This device 

provides transient voltage surge protection for two pairs of communication 

circuits, up to eight pairs of any combination of initiating circuits and notifying 

circuits, and AC power protection. This product also features field replaceable 

modules and an edge card connection circuit that shields the AC power circuit 

from the loop and comminication circuits .

Installation

Cabinet

Caution: This installation should be performed by a licensed electrician.

Note: Install this device between the field wiring and the alarm panel.

Disconnect system power and loop circuits before beginning installation.

1. Locate an appropriate area for the cabinet near the alarm panel to be protected.

2. Position the TSS cabinet on the finished wall surface and fasten the cabinet 

    to the wall.

3. Remove the appropriate knockouts from the cabinet to facilitate the routing of

    the field wiring and alarm panel supply wiring . Make sure the field wiring and 

    the protected wiring to the alarm panel occupy separate conduit feeds.

4. Pull the field wiring and the alarm panel supply wiring through the appropriate

    knockouts on the cabinet. Make sure to route the AC power wires separately 

    from the loop circuit wires. 

 

DTK-120SRD (120V Series Surge Protector)

Warning !! 

Turn power off at the main circuit breaker panel.

Note: Connect this device in series between the AC power supply wiring and the 

alarm panel AC inputs.

1. Crimp the supplied ring terminals to the connection wires.

2. Connect the Ground (green or bare) supply wire to the ground buss on the 

    back plane. The GROUND on the DTK-120SRD has been factory pre-wired. It is not 

    necessary to make any additional ground connections.

3. Connect the Neutral (white) supply wire to the NEUTRAL terminal on the Input side. 

4. Connect the Phase (black) supply wire to the LINE terminal on the Input side.

5. Connect the Ground, Neutral and Phase wires from the Output side to the alarm

    panel AC inputs.

6. After all connections have been made and metal nuts have been torqued to 10 

    inch pounds, install the plastic protective cover and fasten with the included nylon 

    nuts until snug, then restore power.

11"

12"

12”

9"

4"

NO         C          NC

DRY CONTACT

)

NEUTRAL(

-

)

LOAD: 120VAC, 0.5AMP (MAX)

EXAMPLE MONITORING CIRCUIT

EXAMPLE REMOTE MONITORING

USING FACP FOR NOTIFICATION

DTK-120SRD

DRY CONTACT CIRCUIT INFORMATION

DITEK CORPORATION

One DITEK Center 1720 Starkey Road Largo, Fl 33771

       1-800-753-2345         www.ditekcorp.com

191519 INT-100099-001 Rev 5

       GROUNDED 

120 VAC POWER TO 

       ALARM PANEL.

(Installer Provided)

    GROUND WIRE TO 

      GROUND BUSS

     (Chassis Ground)

   (Factory Pre-Wired)

           GROUNDED 

      120 VAC POWER

(Installer Provided) 

Ground Buss

DTK-5MB Ground

(Factory Pre-Wired)

Ground For Future Use On

Additional Bases (Installer Provided) 

SURGE PROTECTIVE DEVICE

DTK-120SRD

CAUTION !!!

HIGH VOLTAGE

MADE IN USA

WWW.DITEKCORP.COM