background image

dIXEL

Operating and Instructions Manual

1592006100

1592006100  XB570L GB r1.0 04.11.2004.doc

XB570L

4/6

15.3.6   “rtC”: clock management (for XB570L only)

It contains the real time clock parameters:

SEC: seconds 

(00÷59);

Min: Minutes 

(00÷59);

Hou Current hour 

(1÷24)

7dY

day of the week

  (

Mon

 = Monday,  

tue

 = Tuesday, 

Wed

  =

Wednesday, 

thu

 = Thursday, 

Fri

 = Friday, 

Sat

 = Saturday, 

Sun

  =

Sunday).

dAY: day of the month 

(1÷31)

Mon: number of the month 

(1÷12)

YEA: year

 (0÷99)

15.3.7   “ALr”: alarms display

This function displays any alarm messages.

15.3.8  “Prt”: printer management

This menu is used for the management of the printer. It contains the
parameters:

PrP 

printer presence: (Yes/no) Enabling or disabling the printer

itP: 

printing interval: (0.0÷30.0 min) It sets the interval of printing.

PbP: Which probe print: 

(,

iP:

 Only the Insert probe; 

rP:

 Only the room

probe; 

irP: 

The Insert and the room probe; 

irE:

 All the probe)

PtH:

 (yes/no) it enables or disables the printing during the holding

phase.

15.3.9 “tSt”:

 it starts the instrument self test

.

15.3.10  “Out”: exits from menu.

16.  Accessing “Pr2” and SECURITY CODE input

To access parameters in “

Pr2

” a security code is required.

1.  Enter Function Menu, select label “

Pr2

” and press the “

SET

” key. The

“PAS” flashing message is displayed, shortly followed by “0 _ _” with a
flashing zero.

2. Use 

“UP”

 or 

“DOWN”

 to input the security code in the flashing digit;

3.  Confirm the figure by pressing “

SET

”.

4.  Repeat operations 2 and 3 for the other digits.
5.  If the security code is correct the access to “

Pr2

” is enabled by pressing

SET

” on the last digit, otherwise the “rtC” menu is shown.

If no key is pressed for more than 15 seconds the instrument reverts to room
temperature display mode.

The default SECURITY CODE is 

321 .

NOTA1: 

the general security code is 

981

. (please refer to parameter PAS)

NOTE2

: each parameter in “Pr2” can be removed or put into “Pr1” (user

level) by pressing 

“SET

è

. In Pr2 when a parameter is present in “Pr1” or

“rtC” LED 

 is on.

17.  List of parameters

REGULATION

HyIntervention differential for set point:

 (0,1 

÷

 12,0 /0,1°C/1°F), always

positive. Compressor cut IN is Set Point Plus Differential (Hy).
Compressor cut OUT is when the temperature reaches the set point.

AC Anti-short cycle delay

: (0÷30 min) minimum interval between the

compressor stop and the following restart.

1c2 Second compressor setting: (enabled only if OAC=C2)

The fourth relay work as second compressor if OAC=Co2.
Second compressor operates on set + OAS. (whit set= set loaded during
the current phase). It starts oAt min. after the first compressor
The following table shows how it works:

Cycle

Holding

1c2=0

C1 ON; C2 On

C1 on; C2 On

1c2=1

C1 on; C2 On

C1 on C2 off

1c2=2

C1 on; C2 off

C1 on; C2 On

1c2=3

C1 on; C2 off

C1 off; C2 On

rPOThermostat probe calibration 

(-12,0 

÷

 12,0; res. 0,1 °C /1°F)

EPP Evaporator probe presence (not present in the XB350C): 

(no / YES)

no:

 not present (timed defrost); 

YES:

 present (end defrost )

EPO Evaporator probe calibration (not present in the XB350C): 

(-12,0 

÷

12,0; res. 0,1 °C /1°F)

iPP Insert probe presence (

no / YES) 

no:

 not present; 

YES:

 present.

iPO Insert probe calibration 

(-12,0 

÷

 12,0; res. 0,1 °C /1°F)

CF Temperature measurement unit

: °C =Celsius; °F =Fahrenheit

rES Resolution (for °C)

in

: integer; 

de

: with decimal point

PAU Time of stand by: 

(0 

÷

 60min) after this time the controller restart the

cycle

PFt Maximum acceptable duration of power failure: 

(0 

÷

 250 min) if power

failure duration is less than PFt, the cycle restarts from the same point at
which it was stopped otherwise the cycle restarts from the beginning of
the current phase.

iPd Temperature difference for the automatic recognition of the insert

probe:

 (0 

÷

 30; ris.1 °C/1°F) if the difference of temperature between the

insert probe and the thermostat probe is less than iPd, the selected cycle
is made by time.

iPtTime delay for the automatic recognition of the insert probe:

(0÷255sec, with 0 only timed cycles are done) time between the start of
a cycle and the comparison of the temperature of the thermostat probe
and the insert probe to recognising if the insert probe is used.

Con Compressor ON time with faulty probe

: (0

÷

 255 min) time during

which the compressor is active in case of faulty thermostat probe. With
COn=0 compressor is always OFF

COF Compressor OFF time with faulty probe

: (0÷255 min) time during

which the compressor is off in case of faulty thermostat probe. With
COF=0 compressor is always active

diC Digital input operating mode 

(EAL, bAL, dor)

EAL: 

external alarm; 

bAL: 

serious alarm;  

dor: 

door open function

diP: digital input polarity:

 (OP÷CL)select if the digital input is activated by

opening or closing the contact. OP= opening; CL=closing

did: digital input delay 

(0÷255 min)  delay between digital input activation

and his signalling for configurable or door opened alarm.

NOTE: 

with 

diC=EAL did 

has to be 

different from zero

.

OAC: AUX output configuration: 

(AL, Li, UL, Ip, AA, rE, dF, C2)

AL:

 alarm output; 

Li: 

light of the cabinet; 

UL: 

for the ultra-violet light (It is

actionable only when the controller is in OFF position); 

Ip:

 to extract the

insert probe

 

(It is actionable only when the controller is in OFF position);

AA: 

anti - condensation; 

rE:

 the IV relay works as a thermostat, with

direct action (cooling) (OAH>0), and inverse actions (heating) (OAH<0);

dF: 

the IV relay is activated during the defrost, at the end of the defrost it

remains ON for the OAt time; 

C2: 

second compressor. See 1c2

parameter for different settings.

OAP

AUX output polarity (

OP 

÷

 CL) 

OP

= normally open; if it is ON the

terminals 6-8 are closed. 

CL

= normally closed; if it is ON the terminals 6-

7 are closed.

OAt  AUX output timer

: (0÷255 min) time in which the AUX output stays ON.

It is enabled when OAC = Li or UL or Ip or AA or dF.

OAS Set point for AUX output 

(-50÷50; ris.1 °C/ 1°F)

OAH Differential for AUX output: 

(-12.0

÷

12,0; ris.0,1°C/1°F, always 

0)

Intervention differential for the set point of the auxiliary, with OAH<0 the
action is for heating, with OAH>0 it is for cooling. 

COOLING:

 AUX cut IN

is OAS Plus Differential (OAH>0). AUX cut OUT is when the temperature
reaches the set point OAS.

 

HEATING:

 AUX cut IN is OAS Plus Differential (OAH<0). AUX cut OUT is

when the temperature reaches the set point OAS.

OAi Probe selection for the AUX output (rP, EP, iP) 

rP = thermostat probe,

EP = evaporator probe; iP = insert probe

DEFROST

tdF Defrost type (not present in the XB350C)

: (

rE

= electrical heater; 

in

  =

hot gas).

dPO Defrost before the holding: no

= no defrost;  

YES

= defrost at the start

of a holding cycle.

IdF Interval between defrost cycles

: (0.1

÷

 24.0; res. 10 min) Determines

the time interval between the beginning of two defrost cycles. (with 0.0
the defrost is disabled)

dtE Defrost termination temperature (not present in the XB350C)

: (-

50

÷

50 °C/°F) Sets the temperature measured by the evaporator probe,

which terminates the defrost.

MdF Maximum length for defrost

: (0÷255 min)  When EPP = no (timed

defrost) it sets the defrost duration, when EPP = YES (defrost
termination based on temperature) it sets the maximum length for
defrost.

dFd Temperature displayed during defrost

: (rt , it, SEt, dEF

) rt: 

real

temperature; 

it:

 temperature at the start of defrost; 

SEt:

 set point; 

dEF:

“dEF” message

Fdt Drip time (not present in the XB350C)

: (0 

÷

 60 min) Time interval

between reaching defrost termination temperature and the restoring of
the controllers' normal operation. This time allows the evaporator to
eliminate water drops that might have formed during defrost.

FANS

FnC Fans operating mode during the holding phase

:

C-n

= runs with the compressor, OFF during defrost; 

o-n

 = continuous

mode, OFF during defrost; 

C-Y

 = runs with the compressor, ON during

defrost; 

o-Y

 = continuous mode, ON during defrost;

FSt Fan stop temperature

: (-50÷50°C/°F; res. 1°C/1°F) if the temperature,

detected by the evaporator probe is above FSt fans are stopped. It
serves to avoid blowing warm air around the room.

AFH Differential for the stop temperature and for the alarm 

(0.1 

÷

 25.0

°C; ris.0.1°C/1°F) Fans carry on working

 

when the temperature reaches

the FSt-AFH value, the temperature alarm recovers when the
temperature is AFH degrees below the alarm set.

Fnd Fan delay after defrost:

 (0 

÷

 255 min) The time interval between end of

defrost and evaporator fans start.

ALARM

ALU MAXIMUM temperature alarm

: (1 

÷

 50 °C/°F) When the “SET+ALU”

temperature is reached  the alarm is enabled, (possibly after the “Ald”
delay time).

Summary of Contents for XB570L

Page 1: ...tures The series XB has been created for fast chilling or freezing goods according to international food safety standards There are FOUR types of cycles The CYCLES Cy1 Cy2 Cy3 Cy4 are pre set according to the most common cycles used in food safety applications the user can select one of them according to his own requirements and modify it as he wants Any cycle can be manually terminated before the...

Page 2: ...ys C1 C2 C3 C4 the related led will be lighted and the cycle will be selected NOTE to pass from a cycle to another one simply push the related key HOLD PHASE To select the old phase deselect the enabled cycle pushing the related key ES Cycle 1 is selected its led is oon push the C1 key the led will be turn off and the hold phase will be enabled 2 Cycles are pre set with the following values 1 Cy1 ...

Page 3: ...eaches the iS3 value normally 18 C 0 F in any case it ends when the maximum time Pd1 Pd2 Pd3 has expired 14 3 4 End of the Blast Chill cycle and starting of the Hold Mode When the Blast Chiller cycle ends an alarm signal is generated buzzer and alarm relay is turned ON the display shows the message End alternating with the room temperature The alarm automatically stops after 30min or by pressing a...

Page 4: ...sor ON time with faulty probe 0 255 min time during which the compressor is active in case of faulty thermostat probe With COn 0 compressor is always OFF COF Compressor OFF time with faulty probe 0 255 min time during which the compressor is off in case of faulty thermostat probe With COF 0 compressor is always active diC Digital input operating mode EAL bAL dor EAL external alarm bAL serious alar...

Page 5: ...the DOWN key or by closing the door 19 1 3 OAC UL UV light for a sterilisation cycle It is used for a sterilisation cycle of the machine It can be enabled ONLY WHEN THE CONTROLLER IS NOT WORKING or when a manual defrost is running The ultra violet light stays on for the OAt time It can be switched off before the OAt time by pressing the DOWN key NOTE with OAt 0 it can be switched off only by press...

Page 6: ... rS2 30 C 22 F Pd3 OFF rS1 30 C 22 F Pd2 OFF dbH yes Pd1 4 0 iS3 18 C 0 F HdS 18 C 0 F Cy4 direct fast freezing without holding dbC no iS2 18 C 0 F rS3 30 C 22 F iS1 18 C 0 F rS2 30 C 22 F Pd3 OFF rS1 30 C 22 F Pd2 OFF dbH no Pd1 4 0 iS3 18 C 0 F HdS OFF 24 Standard Values of the parameters Lab Description XB570L C F Regulation Hy differential 2 4 AC Anti short cycle delay 1 1c2 Second compressor ...

Reviews: