background image

 

1592025700 IPROFAMILY stp GB 2012.08.08.doc 

iPro Series 

 

33/72 

4.4.2 

Description of the inputs and outputs 

 

Input 

No. 

Type of Input 

Description 

1 Supply 

Reference “-“/GND power (24Vac or 24Vdc) 

2 Supply 

Reference “+“ power supply (24Vac or 24Vdc)

 

Remote Display 

Connection for VISOGRAPH remote terminal (Vnr) 

Remote Display 

Connection for VISOGRAPH remote terminal (+) 

Remote Display  

Connection for VISOGRAPH remote terminal (-) 

RS485 Slave 

RS485 Slave connection (-) 

RS485 Slave 

RS485 Slave connection (+) 

Serial Port 

LAN or RS485 MASTER Connection (-) – depend on the model 

Serial Port 

LAN or RS485 MASTER Connection (+) – depend on the model 

10 

CAN 

CANBUS connection (-) 

11 

CAN 

CANBUS connection (+) 

 
 

4.4.3 Technical 

specifications 

 
 
 

4.4.3.1 Wiring diagrams 

 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 

Summary of Contents for iPro SERIES

Page 1: ...iPro SERIES V 3 2 ...

Page 2: ......

Page 3: ...4 Digital outputs 24 4 2 3 5 Wiring diagrams 25 4 2 3 6 Mechanical specifications 25 4 2 3 7 Electrical specifications 25 4 2 3 8 Plastic container 26 4 2 3 9 Product certifications 26 4 3 IPRO 4 DIN IPG100D IPG200D IPC100E RANGES 27 4 3 1 Description of the connections 27 4 3 2 Description of the inputs and outputs 28 4 3 3 Technical specifications 29 4 3 3 1 Analogue inputs 29 4 3 3 2 Digital in...

Page 4: ...5 INTERFACE 52 5 1 VISOGRAPH 52 5 1 1 Specifications 52 5 1 2 Connections 53 5 1 3 Options menu 53 5 1 4 Dimensions 54 6 MEANING OF THE LEDS AND JUMPERS IN THE VARIOUS DEVICES 55 6 1 PROGRAMMABLE CONTROLLERS 55 6 2 EXPANSION MODULES 55 7 INSTALLATION 56 7 1 GENERAL RULES 56 7 2 POWER SUPPLY 56 7 3 CONNECTION OF THE ANALOGUE INPUTS 57 7 3 1 Temperature probes NTC and PTC 57 7 3 2 Pressure transduce...

Page 5: ...applications in industrial environments it may be useful to use the main filters our mod FT1 in parallel to the inductive loads The customer shall bear full responsibility and risk for product configuration in order to achieve the results pertaining to installation and or final equipment system Upon the customer s request and following a specific agreement Dixell s r l may be present during the st...

Page 6: ... unchanged functionality 1 1 PRODUCT DISPOSAL WEEE With reference to Directive 2002 96 EC of the European Parliament and of the Council of 27 January 2003 and to the relative national legislation please note that There lies the obligation not to dispose of electrical and electronic waste as municipal waste but to separate the waste Public or private collection points must be used to dispose of the...

Page 7: ...ts of programmable controllers I O expansions drivers for electronic valves and graphical interfaces adapted to cover any type of application in the air conditioning sector cooling sector and any relative area As the system is one of the most technologically advanced it is flexible and can be customised for it to be adapted to the user s particular requirements ...

Page 8: ...ion Chart Flow Chart FBD IEC 61499 provides all programmers with access to the processing environment Thanks also to the extensive libraries of blocks already developed by Dixell the processing and debug times are reduced The SIMULATION verification of the application without using the controller and DEBUG options verification of the actual application within the controller allow the user to block...

Page 9: ...D display has the following features 240x96 pixel LCD graphic display 32 bit processor Multilingual in ASCII or UNICODE version 8 fully programmable keys Panel or wall mounted The LED display only for the IPS versions has the following features Configurable digits and icons 6 fully programmable keys ...

Page 10: ...ctable connectors o IPX215D 15 relay spring connectors 4 DIN versions IPRO GENIUS o IPG108D 8 relays no application disconnectable screw connectors o IPG208D 8 relays no application spring screw connectors o IPG108E 8 relays LED display without application diconnectable screw connectors o IPG208E 8 relays LED display without application spring screw connectors IPRO CHILL o IPC108E 8 relays LED dis...

Page 11: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 11 72 4 1 IPRO GENIUS AND IPRO CHILL IPG100D IPC100D RANGES ...

Page 12: ...ion is active Closed circuit terminal Term RS485 Slave connector Rx and Tx LED to indicate that communication is active Closed circuit terminal Term RS485 Master connector Rx and Tx LED to indicate that communication is active Closed circuit terminal Term Digital relay outputs 115D 110D 415D 410D versions 3 NO relays 1 changeover relay 1 common Digital relay outputs 115D 110D 415D 410D versions 6 ...

Page 13: ...nalogue output 3 0 10V 24 Out4 Analogue output 4 0 10V 25 GND Additional power reference 12Vdc and analogue outputs 26 Out5 Analogue output 5 0 10V 4 20mA Relay if TF1 is not used 27 Out6 Analogue output 6 0 10V 4 20mA Relay if TF2 is not used 28 TF1 Analogue output TF1 PWM if Out5 is not used 29 TF2 Analogue output TF2 PWM if Out6 is not used 30 12V Additional power 12Vdc 40 DI1 Opto insulated di...

Page 14: ... 12 13 and 15 MAX 6A 88 C Common relays 12 13 and 15 MAX 6A 89 RL11 Relay 11 normally closed contact 90 C Common relays 11 and 14 MAX 6A 91 RL14 Relay 14 normally open contact 92 RL14 Relay 14 normally closed contact 93 RL15 Relay 15 normally open contact 94 RS485 Master RS485 Master connection 95 RS485 Master RS485 Master connection 96 RS485 Master RS485 Master connection insulated gnd 97 RS485 S...

Page 15: ...ROFAMILY stp GB 2012 08 08 doc iPro Series 15 72 89 RL14 Relay 14 normally open contact 90 RL14 Common relays 14 91 RL15 Relay 15 normally open contact 92 RL15 Common relays 15 93 RL13 Relay 13 normally open contact ...

Page 16: ... prevent the inputs from malfunctioning or being damaged 4 1 3 2 Digital inputs Type configurable via software parameter Opto insulated potential free contact Number of inputs 20 Digital input status variation detection time 100ms in any case it depends on the cycle time set by the user in the given application Notes Do not use live contacts in order to prevent the inputs from being damaged 4 1 3 ...

Page 17: ...roups of relays nor within each group 4 1 3 5 SSR Digital outputs version Type Relays with NO or NC contacts depending on the model Number of outputs 10 or 15 depending on the model Type of output configurable via software parameter Relays with normally open contact RL1 RL2 RL4 RL5 RL6 RL7 RL8 RL9 RL10 RL11 RL12 RL13 RL14 RL15 Relays with changeover contact RL3 Maximum load Relays with normally op...

Page 18: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 18 72 4 1 3 6 Wiring diagrams ...

Page 19: ... or 64MB in 16 bit Internal clock standard 4 1 3 9 Plastic container Mount On a DIN rail EN 50022 DIN 43880 Fastened with screws via the removable plastic flaps Material PC ABS Thermoplastic Self extinguishing V0 UL94 Comparative Tracking Index CTI 300V Colour Black 4 1 3 10 Product certifications Control to classify with the definitions 2 5 1 e 2 5 2 mentioned in the section 2 5 of the general re...

Page 20: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 20 72 4 2 IPRO GENIUS IPG200D RANGE ...

Page 21: ...e connector Rx and Tx LED to indicate that communication is active Closed circuit terminal Term RS485 Master connector Rx and Tx LED to indicate that communication is active Closed circuit terminal Term Digital relay outputs for digital outputs with potential free contacts 3 NO relays 1 common Digital relay outputs for digital outputs with live contacts 3 NO relays 1 common and 2 potential free Ne...

Page 22: ... power 5Vdc 16 12V Additional power 12Vdc 21 Out1 Opto insulated analogue output 1 0 10V 22 Out2 Opto insulated analogue output 2 0 10V 23 Out3 Opto insulated analogue output 3 0 10V 24 Out4 Opto insulated analogue output 4 0 10V 25 GND Common opto insulated analogue output 26 Out5 Analogue output 5 0 10V 4 20mA Opto insulated relay 27 Out6 Analogue output 6 0 10V 4 20mA Opto insulated relay 28 Su...

Page 23: ...mon relays 9 and 10 MAX 6A 87 RL11 Relay 11 normally open contact 88 RL12 Relay 12 normally open contact 89 RL13 Relay 13 normally open contact 90 C Common relays 11 12 13 14 and 15 MAX 6A 91 RL14 Relay 14 normally open contact 92 RL15 Relay 15 normally open contact 93 C Potential free contact MAX 6A 94 RS485 Master RS485 Master connection 95 RS485 Master RS485 Master connection 96 RS485 Master RS...

Page 24: ...he cycle time set by the user in the given application Notes If the digital inputs are used with voltage use another transformer do not use the same secondary of the controller s power in order to prevent the inputs from malfunctioning or being damaged 4 2 3 3 Analogue outputs Type Opto insulated with separate 24Vac dc power supply Number of outputs 6 Type of analogue output configurable via softw...

Page 25: ...ectrical specifications Power Supply 24Vac 10 15 50 60Hz 20 36Vdc Consumption 20VA Vac 15W Vdc Connectors Phoenix quick coupling connectors for low voltage STELVIO 90 screw connectors for digital outputs 250Vac 6A max Microprocessor AT91RM9200 32 bit 200Mhz Permanent FLASH memory 128MB in 8 bit RAM 32MB o 64MB in 16 bit Internal clock standard ...

Page 26: ...xtinguishing V0 UL94 Comparative Tracking Index CTI 300V Colour White 4 2 3 9 Product certifications Control to classify with the definitions 2 5 1 e 2 5 2 mentioned in the section 2 5 of the general requirements EN60730 1 2 5 1 integrated control 2 5 2 incorporated control Electrical safety EN60730 1 Electromagnetic compatibility EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6 EN61000...

Page 27: ...ro Series 27 72 4 3 IPRO 4 DIN IPG100D IPG200D IPC100E RANGES 4 3 1 Description of the connections Connector Description Connector for 24Vac dc power supply Analogue inputs Pb1 Pb6 PbC Additional power 5Vdc 12Vdc GND Analogue outputs Out1 Out4 GND ...

Page 28: ...0 10V 4 20mA Relay 9 Supply Reference power supply 24Vac or 24Vdc 10 Pb4 Configurable analogue input 4 NTC PTC 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 11 Pb5 Configurable analogue input 5 NTC PTC 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 12 Pb6 Configurable analogue input 6 NTC PTC 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 13 PbC Common analogue inputs NTC PTC DI 14 GND Additional power reference 5Vdc and 12Vdc analogue i...

Page 29: ...tage 0 V 0 5V 0 10V input resistance 3 7KΩ Current 0 20mA 4 20mA input resistance 100Ω Digital input status variation detection time 100ms in any case it depends on the cycle time set by the user in the given application Accuracy NTC PTC 1 0 1V 20mV 0 5V 100mV 0 10V 200mV 2 20mA 4 20mA 0 30mA Additional power 12V 200mA in total between 12V and analogue outputs 5v 100mA Notes Any inputs that are po...

Page 30: ...s controlled by these analogue outputs must be powered separately with another transformer do not use the same secondary of the controller s power in order to prevent the outputs from malfunctioning or being damaged 4 3 3 4 Digital outputs Type Relays with NO contacts Number of outputs 8 Type of output configurable via software parameter Relays with normally open contact Maximum load 5A 250Vac SPS...

Page 31: ... 32MB in 8 bit RAM 32MB in 16 Internal clock standard 4 3 3 8 Plastic container Mount On a DIN rail EN 50022 DIN 43880 Fastened with screws via the removable plastic flaps Material PC ABS Thermoplastic Self extinguishing V0 UL94 Comparative Tracking Index CTI 300V Colour Black or White depending on the model 4 3 3 9 USB ETHERNET Adapter The IPS range of programmable controllers can be connected to...

Page 32: ...terminal per iPRO RS485 Slave connector Serial port connector LAN or RS485 CANBUS connector for expansion and driver for electroni expansion valve Communication leds USB port for downloads BIOS ISaGRAF application maps of parameters remote display applications network configuration website and uploads log files Ethernet port for TCP IP connections SIM CARD slot only for version with GPRS modem Con...

Page 33: ...n for VISOGRAPH remote terminal Vnr 4 Remote Display Connection for VISOGRAPH remote terminal 5 Remote Display Connection for VISOGRAPH remote terminal 6 RS485 Slave RS485 Slave connection 7 RS485 Slave RS485 Slave connection 8 Serial Port LAN or RS485 MASTER Connection depend on the model 9 Serial Port LAN or RS485 MASTER Connection depend on the model 10 CAN CANBUS connection 11 CAN CANBUS conne...

Page 34: ...rs STELVIO 90 screw connectors for digital outputs 250Vac 6A max Microprocessor AT91SAM9260 32 bit 200Mhz Permanent FLASH memory 128MB in 8 RAM 32MB in 16 Internal clock standard 4 4 3 4 Plastic container Mount On a DIN rail EN 50022 DIN 43880 Fastened with screws via the removable plastic flaps Material PC ABS Thermoplastic Self extinguishing V0 UL94 Comparative Tracking Index CTI 300V Colour Bla...

Page 35: ...DI3 DIC Additional power 5Vdc 12Vdc GND Analogue outputs Out1 Out3 GND Analogue inputs Pb6 Pb7 PbC Additional power 5Vdc 12Vdc GND Digital relay outputs 6 NO relays 2 common CANBUS Connector Rx and Tx LED to indicate that communication is active Closed circuit terminal Term LAN serial port connector Dip switch to set the address of the device Green LED to indicate the presence of power Red status ...

Page 36: ... 3 14 Pbc Common analogue inputs NTC PTC PT1000 DI 15 GND Additional power reference 5Vdc and 12Vdc and analogue inputs 0 20mA 4 20mA 0 10V 0 1V 0 5V 16 5V Additional power 5Vdc 20 GND Additional power reference 5Vdc 12Vdc and analogue outputs 21 Out1 Analogue output 1 0 10V 22 Out2 Analogue output 2 0 10V 23 Out3 Analogue output 3 0 10V 24 Pb6 Configurable analogue input 1 NTC PTC PT1000 0 20mA 4...

Page 37: ...potential free contact Number of inputs 3 Digital input status variation detection time 100ms in any case it depends on the cycle time set by the user in the given application Notes Do not use live contacts in order to prevent the inputs from being damaged 4 5 3 3 Analogue outputs Type Non opto insulated internal power Number of outputs 3 Type of analogue output configurable via software parameter...

Page 38: ...rical specifications Power Supply 24Vac 10 15 50 60Hz 20 36Vdc Consumption 10VA Vac 10W Vdc Connectors Molex connectors with low voltage wiring SELECOM CIVILUX connectors for digital outputs 250Vac 6A max or with a different order code Phoenix quick coupling connectors for low voltage STELVIO 90 screw connectors for digital outputs 250Vac 6A max ...

Page 39: ... PC ABS Thermoplastic Self extinguishing V0 UL94 Comparative Tracking Index CTI 300V Colour Black 4 5 3 9 Setting the address of the device The address of the device is set via a dip switch and numbering is binary as shown in the table below If the address is changed while the device is switched on to confirm the new address remember to switch off and switch on again the device Not used ...

Page 40: ...lated analogue output Potential free opto insulated digital inputs DI1 DI20 DIC Opto insulated 24Vac dc digital inputs DI1 DI20 GND LAN serial port connector Rx and Tx LED to indicate that communication is active CANBUS Connector Rx and Tx LED to indicate that communication is active Closed circuit terminal Term Dip switch to set the address of the device Digital relay outputs 3 NO relays 1 change...

Page 41: ...0V 0 1V 0 5V DI 11 Pb7 Configurable analogue input 7 NTC PTC PT1000 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 12 Pb8 Configurable analogue input 8 NTC PTC PT1000 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 13 Pb9 Configurable analogue input 9 NTC PTC PT1000 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 14 Pb10 Configurable analogue input 10 NTC PTC PT1000 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 15 5V Additional power 5Vdc 16 12V Additio...

Page 42: ...lays 5 8 and 9 MAX 6A 77 RL5 Relay 5 normally open contact 78 RL6 Relay 6 normally open contact 79 RL7 Relay 7 normally open contact 80 RL8 Relay 8 normally open contact 81 RL9 Relay 9 normally open contact 82 RL10 Relay 10 normally open contact 83 C Common relays 6 7 and 10 MAX 6A 84 RL11 Relay 11 normally open contact 85 RL12 Relay 12 normally open contact 86 RL13 Relay 13 normally open contact ...

Page 43: ... with another transformer do not use the same secondary of the controller s power in order to prevent the inputs from malfunctioning or being damaged 4 6 3 2 Digital inputs Type configurable via software parameter Opto insulated potential free or live contact 24Vac dc External power 24Vac dc 20 Number of inputs 20 Digital input status variation detection time 100ms in any case it depends on the cy...

Page 44: ...RL17 RL18 RL19 Maximum load Relays with normally open contact 5A 250Vac SPST 5 2 A Relays with changeover contact 8A 250Vac SPDT 8 3 A SSR relays with normally open contact 1A 12 250Vac only in AC load minimum current is 50mA equivalent to 12W 250Vac internal impedance 300KΩ current 0 2mA at 250Vac with an open contact Notes Verify the capacity of the output used There is double insulation between...

Page 45: ...6A max 4 6 3 8 Plastic container Mount On a DIN rail EN 50022 DIN 43880 Fastened with screws via the removable plastic flaps Material PC ABS Thermoplastic Self extinguishing V0 UL94 Comparative Tracking Index CTI 300V Colour Black 4 6 3 9 Setting the address of the device The address of the device is set via a dip switch and numbering is binary as shown in the table below If the address is changed...

Page 46: ...gital inputs DI1 DI20 GND LAN serial port connector Rx and Tx LED to indicate that communication is active CANBUS Connector Rx and Tx LED to indicate that communication is active Closed circuit terminal Term Dip switch to set the address of the device Digital relay outputs 3 NO relays 1 common and 2 potential free Neutral Digital relay outputs 5 NO relays 1 common and 2 potential free Neutral Digi...

Page 47: ...DI 11 Pb7 Configurable analogue input 7 NTC PTC PT1000 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 12 Pb8 Configurable analogue input 8 NTC PTC PT1000 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 13 Pb9 Configurable analogue input 9 NTC PTC PT1000 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 14 Pb10 Configurable analogue input 10 NTC PTC PT1000 0 20mA 4 20mA 0 10V 0 1V 0 5V DI 15 5V Additional power 5Vdc 16 12V Additional power 12V...

Page 48: ... open contact 77 RL5 Relay 5 normally closed contact 78 RL6 Relay 6 normally closed contact 79 RL7 Relay 7 normally closed contact 80 P Common relays 4 5 6 7 and 8 MAX 6A 81 RL8 Relay 8 normally closed contact 82 N Potential free contact MAX 6A 83 N Potential free contact MAX 6A 84 RL9 Relay 9 normally closed contact 85 RL10 Relay 10 normally closed contact 86 P Common relays 9 and 10 MAX 6A 87 RL...

Page 49: ... another transformer do not use the same secondary of the controller s power in order to prevent the inputs from malfunctioning or being damaged 4 7 3 2 Digital inputs Type configurable via software parameter Opto insulated potential free or live contact 24Vac dc External power 24Vac dc 20 Number of inputs 20 Digital input status variation detection time 100ms in any case it depends on the cycle t...

Page 50: ...elays RL16 RL17 RL18 RL19 Maximum load Relays with normally open contact 5A 250Vac SPST 5 2 A SSR relays with normally open contact 1A 12 250Vac only in AC load minimum current is 50mA equivalent to 12W 250Vac internal impedance 300KΩ current 0 2mA at 250Vac with an open contact Notes Verify the capacity of the output used There is double insulation between the digital outputs and the low voltage ...

Page 51: ...0Vac 6A max 4 7 3 8 Plastic container Mount On a DIN rail EN 50022 DIN 43880 Fastened with screws via the removable plastic flaps Material PC ABS Thermoplastic Self extinguishing V0 UL94 Comparative Tracking Index CTI 300V Colour White 4 7 3 9 Setting the address of the device The address of the device is set via a dip switch and numbering is binary as shown in the table below If the address is ch...

Page 52: ... the operations to be implemented The displays differ according to the model VGIPG for IPG100 versions VGIPC for IPC100 versions 5 1 1 Specifications LCD graphic display FSTN Graphic resolution 240x96 Dots 32 bit microprocessor White backlight ASCII or UNICODE characters used depending on the model 8 fully programmable keys Programmable display and keys via VISOPROG software Application resident i...

Page 53: ...s it is recommended to contact Dixell so as to prevent the device from being damaged Option 5 PROGRAM INFO displays the information of the application resident in the Visograph Option 6 SETTINGS allows the user to set certain configurations ADR VISOGRAPH if two Visograph s are used with one iPRO set two different addresses CONTRAST to adjust the contrast of the display BACKLIGHT the display backli...

Page 54: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 54 72 5 1 4 Dimensions ...

Page 55: ... JMP1 JMP1 if the JMP1 jumper is short circuited the system creates a virtual IP in order to have access to the internal website The default IP address is 192 168 0 250 the IP address set in the iPRO always remains the same Remove the Jumper switch the iPRO off and on again to restore the system back to the previous conditions CAUTION this mode can only be used if the FIRMWARE version of the iPRO ...

Page 56: ...tallation process in order to prevent the device from malfunctioning Separate the signal cables from the power cables it is recommended to use BELDEN 8772 type shielded cables Separate the cables of the analogue inputs from those of the digital inputs and the serial line cables from the power cables resistive as well as inductive in order to prevent malfunction due to electromagnetic interference ...

Page 57: ...h sensor must be connected through one of the inputs from Pb1 to Pb10 and the common PbC as shown in the diagram below IPG IPC IPG IPC 4 DIN Recommendations follow the diagram of the device used for the numbering the configuration is determined by the application if used as a digital input potential free not live use the same connection configuration of the sensors 7 3 2 Pressure transducers and c...

Page 58: ...low IPG IPC IPG IPC 4 DIN Recommendations follow the diagram of the device used for the numbering the configuration is determined by the application 7 3 4 Live probes 0 1V 0 5V 0 10V 3 row sensors that require 12Vdc power supply Each sensor must be connected through one of the inputs from Pb1 to Pb10 and the power supply 12V GND as shown in the diagram below IPG IPC IPG IPC 4 DIN Recommendations f...

Page 59: ... Pb10 whereas the power supply as shown in the diagram below This is an example for versions IPG IPC For all the others version verify the correct number of the pin in the connector Recommendations respect the and polarities of the power supply the power supply of the sensor must be separate from that of the programmable controller follow the diagram of the device used for the numbering the config...

Page 60: ...n the model used the digital inputs can be used as potential free or live 24Vac dc digital inputs 7 4 1 Potential free digital inputs IPG100 IPC100 and IPX106D versions IPG200 IPX125D IPX115D IPX215D IPX215D VERSIONS IPG108D IPG208D VERSION special version not standard version Recommendations follow the diagram of the device used for the numbering the configuration is determined by the application...

Page 61: ...he configuration is determined by the application 7 5 CONNECTION OF THE ANALOGUE OUTPUTS Depending on the model and configurations it is possible to use analogue outputs such as 0 10Vdc 4 20mA or PWM the PWM configuration requires the Dixell XVxx module to be used for the fan speed to be controlled NOTE the analogue outputs in certain models are not opto insulated In this case any devices that req...

Page 62: ...doc iPro Series 62 72 7 5 1 0 10V 4 20mA Analogue output for condensation control IPG IPC VERSION IPG108 IPG208 VERSION Recommendations follow the diagram of the device used for the numbering the configuration is determined by the application ...

Page 63: ...200 and 4 DIN Recommendations follow the diagram of the device used for the numbering the configuration is determined by the application 7 5 3 0 10V 4 20mA Proportional analogue output for servomotors actuators IPG IPC IPG 4 DIN Recommendations follow the diagram of the device used for the numbering the configuration is determined by the application ...

Page 64: ...whereas the power supply as shown in the diagram below This is an example for versions IPG IPC For all the others version verify the correct number of the pin in the connector Recommendations respect the and polarities of the power supply the power supply of the device must be separate from that of the programmable controller follow the diagram of the device used for the numbering the configuratio...

Page 65: ...nt connection specifications The relays have been split into groups each with a separate common The same voltage must always be used for the various groups of relays and within each group For the electrical specifications refer to the relative paragraphs of the different models Certain models have SSR relays solid state relay which are suitable to control devices where numerous commutations are re...

Page 66: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 66 72 7 7 CANBUS CONNECTION Recommendations follow the diagram of the device used for the numbering ...

Page 67: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 67 72 7 8 RS485 SLAVE CONNECTIONS Recommendations follow the diagram of the device used for the numbering ...

Page 68: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 68 72 7 9 RS485 MASTER CONNECTION Recommendations follow the diagram of the device used for the numbering ...

Page 69: ..._________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ __________...

Page 70: ..._________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ __________...

Page 71: ..._________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ __________...

Page 72: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 72 72 ...

Reviews: