1592025700 IPROFAMILY stp GB 2012.08.08.doc
iPro Series
43/72
127
RL21
Relay 21 normally open contact
128
C
Common relays 20, 21, 22, 23, 24 and 25 (MAX 6A)
129
RL22
Relay 22 normally open contact
130
RL23
Relay 23 normally open contact
131
RL24
Relay 24 normally open contact
132
C
Common relays 20, 21, 22, 23, 24 and 25 (MAX 6A)
133
RL25
Relay 25 normally open contact
4.6.3 Technical
specifications
4.6.3.1 Analogue inputs
Analogue conversion type:
10-bit A/D converter
Number of inputs:
10
Type of analogue input:
(configurable via software parameter)
NTC Dixell (-50T110°C; 10K
Ω
±1% at 25°C)
PTC Dixell(-55T115°C; 990
Ω
±1% at 25°C)
PT1000 Dixell (-100T150°C; 1K
Ω
at 0°C)
Digital input (potential free contact)
Voltage: 0 - V, 0 - 5V, 0 - 10V (input resistance 15K
Ω
)
Current: 0 - 20mA, 4 - 20mA (input resistance 100
Ω
)
Digital input status variation detection time:
100ms (in any case it depends on the cycle time set by the user in the
given application)
Accuracy:
NTC, PTC, PT1000: ±1°C
0-1V: ±20mV
0-5V: ±100mV
0-10V:±200mV
2-20mA, 4-20mA: ±0.30mA
Additional power:
+12V: 200mA max
+5v: 100mA
Notes:
Any inputs that are powered with a voltage that differs from that supplied
by the device (+12V or +5V) must be powered separately with another
transformer (do not use the same secondary of the controller's power) in
order to prevent the inputs from malfunctioning or being damaged.
4.6.3.2 Digital inputs
Type:
(configurable via software parameter)
Opto-insulated potential free or live contact (24Vac/dc)
External power 24Vac/dc ±20%
Number of inputs:
20
Digital input status variation detection time:
100ms (in any case it depends on the cycle time set by the user in the
given application)
Notes:
If the digital inputs are used with voltage, use another transformer (do not
use the same secondary of the controller's power) in order to prevent the
inputs from malfunctioning or being damaged.
4.6.3.3 Analogue outputs
Type:
Opto-insulated with separate 24Vac/dc power supply
Number of outputs:
6
Type of analogue output:
(configurable via software parameter)
4 fixed outputs 0-10Vdc (Out1 - Out4)
2 configurable outputs 0-10Vdc, 4-20mA (Out5 and Out6)
Maximum load:
40mA (Out1 - Out4)
20mA (Out5 and Out6) max with configured outputs 0-10Vdc
400
Ω
max with configured outputs 4-20mA
22
Ω
per live analogue output
Accuracy:
Out1 - Out4: ±2% full scale
Out5 – Out6: ±2% full scale
Resolution:
8bit
Notes:
The electrical devices controlled by these analogue outputs must be
powered separately with another transformer (do not use the same
secondary of the controller's power) in order to prevent the outputs from
malfunctioning or being damaged.
Summary of Contents for iPro SERIES
Page 1: ...iPro SERIES V 3 2 ...
Page 2: ......
Page 18: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 18 72 4 1 3 6 Wiring diagrams ...
Page 20: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 20 72 4 2 IPRO GENIUS IPG200D RANGE ...
Page 54: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 54 72 5 1 4 Dimensions ...
Page 72: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 72 72 ...