1592030000 xh50_55p r1.2 gb 2011.06.28.doc 

XH50-55P 

1/5 

 

XH50P - XH55P  

Temperature/relative humidity probe with RS485 serial line 

 
1.

 

GENERAL WARNINGS ........................................................................................ 1

 

2.

 

DESCRIPTION..................................................................................................... 1

 

3.

 

FIXING, DIMENSION AND DRILLING .................................................................. 1

 

4.

 

INSTALLATION ADVISE ...................................................................................... 1

 

5.

 

WIRING DIAGRAM .............................................................................................. 2

 

6.

 

DEVICE CONFIGURATION ................................................................................. 2

 

7.

 

CASE CLOSURE ................................................................................................. 2

 

8.

 

CASE OPENING .................................................................................................. 2

 

9.

 

HOTKEY .............................................................................................................. 3

 

10.

 

ANTI-SWEAT HEATERS REGULATION (WITH RELAY OUTPUT) ....................... 3

 

11.

 

ANTI-SWEAT HEATERS REGULATION (WITH ANALOG OUTPUT) .................... 3

 

12.

 

CONFIGURATION AS THERMOSTAT ................................................................. 3

 

13.

 

KNOB (ONLY XH55P) .......................................................................................... 3

 

14.

 

PARAMETER LIST............................................................................................... 3

 

15.

 

RELAY CONFIGURATION ................................................................................... 4

 

16.

 

TECHNICAL DATA .............................................................................................. 5

 

 

1.

 

GENERAL WARNINGS 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy 
and quick reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described 
hereunder. It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the  operating 
limits  avoiding  sudden  temperature  changes  with  high  atmospheric  humidity  to 
prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not 
be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to 
“Dixell S.r.l.” (see address) with a detailed description of the fault. 

 

Consider  the maximum current which can be applied to each relay (see Technical 
Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far 
enough from each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. 
FT1) in parallel with inductive loads could be useful. 

2.

 

DESCRIPTION 

The  XH50P  and  XH55P  devices  (version  with  knob)  are  temperature/relative  humidity 
probe,  but  their  ability  to  calculate  dew-point  of  the  ambient  where  they  are  placed, 

joined  to  the  available  resources  (relay  and  analog  output  depending  on  the  models) 
make them like a regulators. 

  

Thanks  to  its  features,  the  device  can  be  used  a  anti-sweat  heaters  controller  on 
refrigeration  field,  as  a  zone  thermostat  or  as  temperature/humidity  probe  on  air 
conditioning  field.  On  this  manual,  there  are  some  instructions  that  can  be  useful  to 
configure the device on its main applications. 

3.

 

FIXING, DIMENSION AND DRILLING 

During the fixing of the device please, pay attention for the procedure that is described 
below. 

 

 

 

In  order  to  censure  a  correct  functioning  the  device  has  to  be  placed  horizontally  (as 
indicated  by  the figure above) so that the 

dIXEL 

logo can be read, only in this way 

the drilling on the case allow the correct inflow of air into the case. 

 

4.

 

INSTALLATION ADVISE 

In  case  of  XH55P  it’s  necessary  to  mount  the  knob  before 
closing  the  case.  First  of  all,  insert  the  pivot  inside  of  the  knob 

. The insertion of the knob has to be done without effort. The 

pivot  has  a  small  plastic  tooth  in  order  to  guide  you  during  the 
insertion.  Ended  this  operation,  insert  the  other  extremity  of  the 
pivot  into  the  trimmer  that  is  mounted  on  the  board  as  you  can 
see on the following figure. 

 

Please  pay  attention  during  the  fixing  of  the  pivot  on  the  trimmer  because  the  small 
tooth on the knob has to be on the position described by the following figure 

 

 

In case of box 503 installation, the cables should be arrive into the devices through the 
central hole as you can see as follow. 

 

 

Otherwise,  if  you 
need to use wireway 
so  that  you  cannot 
use the central hole, 
it’s  advised  to make 
a  small  hole  on  the 
bottom  of  the  case 
after 

having 

removed  the  cover 
in order to avoid the 
possibility 

to 

damage 

the 

electronic 

board. 

Please  follow  the 
figure nearby. 

 

Summary of Contents for XH50P

Page 1: ...d FT1 in parallel with inductive loads could be useful 2 DESCRIPTION The XH50P and XH55P devices version with knob are temperature relative humidity probe but their ability to calculate dew point of the ambient where they are placed joined to the available resources relay and analog output depending on the models make them like a regulators Thanks to its features the device can be used a anti swea...

Page 2: ...S ADR 1 ADR 1 ADR 2 ADR 3 ADR 4 ADR 5 ADR 6 ADR 7 ADR 8 ADR 9 ADR 10 ADR 11 ADR 12 ADR 13 ADR 14 ADR 15 ADR 16 ADR 17 ADR 18 ADR 19 ADR 20 ADR 21 ADR 22 ADR 23 ADR 24 ADR 25 ADR 26 ADR 27 ADR 28 ADR 29 ADR 30 ADR 31 With the selectors 6 and 7 it s possible to configure the internal external temperature probe Please see the following table The probe used to calculate the dew point is the internal p...

Page 3: ...mode By changing the parameter it s possible to invert the action 13 KNOB ONLY XH55P In case of XH55P it s present a knob that permits to set an offset respect to the set point of 3 C this value can be changed with Ltr and Utr parameters If the knob is completely turned off all the output are switched off 14 PARAMETER LIST Set Regulation set point is the set point for relay or analog output regula...

Page 4: ... this case the SET and Hy are used For rLC Man the relay works as manual mode its output percentage PWM is roP so if roP 0 the relay is always OFF if roP 100 the relay is always ON Ltr Lower trimmer offset only for XH55P Offset added to setpoint when the trimmer is at minimum value Utr Upper trimmer offset only for XH55P Offset added to setpoint when the trimmer is at maximum value tAr PWM period ...

Page 5: ...g output percentage during probe error 0 100 0 rLS Relay presence no 0 YES 1 YES rLC Relay configuration nP 0 Mod 1 dEP 2 tEr 3 MAn 4 dEP Ltr Lower trimmer offset Only for XH55P 12 0 C Utr 21 F Utr 3 0 Utr Upper trimmer offset Only for XH55P Ltr 12 0 C Ltr 21 F 3 0 tAr PWM cycle Period 10 255 min 10 LrL Minimum PWM percentage 0 urL 0 urL Maximum PWM percentage LrL 100 100 rOP MANUAL MODE Relay out...

Reviews: