XR30CX 

3/4 

nPS Pressure switch number:

 (0 

÷

15) Number of activation of the pressure switch, during 

the “

did

” interval, before signalling the alarm event (I2F= PAL).  

If the nPS activation in the did time is reached, switch off and on the instrument to 
restart normal regulation. 

odc  Compressor status with door open:

  

no,

 

Fan

 = normal; 

CPr

F_C

 = Compressor OFF.  

rrd  Outputs restart after doA alarm: no = 

outputs not affected by the doA alarm;  

yES = 

outputs restart with the doA alarm;  

HES Temperature increase during the Energy Saving cycle :

 (-30,0°C

÷

30,0°C/-22÷86°F) 

it sets the increasing value of the set point during the Energy Saving cycle.  

OTHER 
Adr  Serial  address

 (1÷244): Identifies the instrument address when connected to a 

ModBUS compatible monitoring system. 

PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC 

probe, 

ntc = 

NTC probe. 

onF  on/off key enabling: nu = 

disabled; 

oFF = 

enabled; 

ES = not set it

dP1  Thermostat probe display 
dP3  Third probe display

optional

dP4  Fourth probe display

rSE  Real set point: 

(readable only), it shows the set point used during the energy saving 

cycle or during the continuous cycle. 

rEL Software release 

for internal use

Ptb  Parameter table code: 

readable only

8.

 

DIGITAL INPUT (ENABLED WITH P3P = N) 

The free voltage digital input is programmable in different configurations by the “

i1F

” 

parameter. 

8.1

 

DOOR SWITCH INPUT  (i1F = dor) 

It signals the door status and the corresponding relay output status through the “

odc

” 

parameter: 

no,

 

Fan

 = normal (any change); 

CPr, 

  

F_C

 = Compressor OFF. 

Since the door is opened, after the delay time set through parameter “

did

”, the door alarm is 

enabled, the display shows the message “

dA

” and 

the regulation restarts is rtr = yES.

 The 

alarm stops as soon as the external digital input is disabled again. With the door open, the 
high and low temperature alarms are disabled. 

8.2

 

GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling 

the “

EAL

” alarm message. The outputs status don’t change. The alarm stops just after the 

digital input is de-activated. 

8.3

 

SERIOUS ALARM MODE (i1F = bAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

CA

” 

alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the 
digital input is de-activated. 

8.4

 

PRESSURE SWITCH (i1F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number 

of activation of  the “

nPS

” parameter, the “

CA

” pressure alarm message will be displayed. The 

compressor and the regulation are stopped. When the digital input is ON the compressor is 
always OFF. 

If the nPS activation in the did time is reached, switch off and on the instrument to 
restart normal regulation. 

8.5

 

START DEFROST (i1F = dFr) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal 
regulation will restart only if the digital input is disabled otherwise the instrument will wait until 
the “MdF” safety time is expired. 

8.6

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F = Htr) 

This function allows to invert the regulation of the controller: from cooling to heating and 
viceversa. 

8.7

 

ENERGY SAVING (i1F = ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ 
HES (parameter) sum. This function is enabled until the digital input is activated. 

8.8

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameter. 

i1P=CL

: the input is activated by closing the contact.

 

i1P=OP

: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector, allows by means of the 
external TTL/RS485 converter, 

XJ485-CX

, to connect the instrument to a monitoring system 

ModBUS-RTU

 compatible  such as the  X-WEB500/3000/300. 

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the HOY 
KEY connector. The X-REP output 

EXCLUDES 

 the serial connection.

 

 

To connect the X-REP to the 
instrument the following 
connectors must be used CAB-
51F(1m), CAB-52F(2m), CAB-
55F(5m), 

11.

 

INSTALLATION AND MOUNTING 

 

Instrument 

XR30CX

 shall be mounted on vertical panel, in a 

29x71 mm hole, and fixed using the special bracket supplied.  
The temperature range allowed for correct operation is 0

÷

60 

°C. Avoid places subject to strong vibrations, corrosive 
gases, excessive dirt or humidity. The same 
recommendations apply to probes. Let air circulate by the 
cooling holes. 
 

12.

 

ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up 
to 2,5 mm

2

. Before connecting cables make sure the power supply complies with the 

instrument’s requirements. Separate the probe cables from the power supply cables, from the 
outputs and the power connections. Do not exceed the maximum current allowed on each 
relay, in case of heavier loads use a suitable external relay. 

12.1

 

PROBE CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 
infiltration. It is recommended to place the thermostat probe away from air streams to correctly 
measure the average room temperature. Place the defrost termination probe among the 
evaporator fins in the coldest place, where most ice is formed, far from heaters or from the 
warmest place during defrost, to prevent premature defrost termination. 

13.

 

HOW TO USE THE HOT KEY  

13.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message 

appears followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

 key 

if you want to restart the upload again or remove the “

Hot key

” to abort the operation. 

13.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn the 

Controller ON. 

3.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Controller 

memory, the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and 

then on if you want to restart the download again or remove the “

Hot key

” to abort the 

operation. 

14.

 

ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. “Con” and 
“COF” 

“P3” 

Third probe  failure 

Outputs unchanged 

“P4” 

Fourth probe  failure 

Outputs unchanged 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

"HA2" 

Condenser high temperature 

It depends on the “Ac2” parameter 

"LA2" 

Condenser low temperature 

It depends on the “bLL” parameter 

“dA” 

Door open 

Compressor according to rrd 

“EA”  

External alarm 

Output unchanged. 

“CA”  

Serious 

external 

alarm 

(i1F=bAL) 

All outputs OFF. 

“CA” Pressure 

switch 

alarm 

(i1F=PAL) 

All outputs OFF 

14.1

 

ALARM RECOVERY  

Probe alarms 

P1

”, “

P3

” and “

P4

” start some seconds after the fault in the related probe; they 

automatically stop some seconds after the probe restarts normal operation. Check 
connections before replacing the probe. 
Temperature alarms “

HA

”, “

LA

” “

HA2

” and “

LA2

” automatically stop as soon as the 

temperature returns to normal values. 
Alarms 

“EA”

 and 

“CA” 

(with i1F=bAL)

 

recover as soon as the digital input is disabled. 

Alarm “

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument. 

14.2

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode

: none parameter is present in Pr1 

On the display

 or in dP2, dP3, dP4: the selected probe is nor enabled 

noA 

None alarm is recorded.

 

Summary of Contents for XR30CX

Page 1: ...ut can operate as third temperature probe The HOT KEY output allows to connect the unit by means of the external module XJ485 CX to a network line ModBUS RTU compatible such as the dIXEL monitoring units of X WEB family It allows to program the controller by means the HOT KEY programming keyboard The instrument is fully configurable through special parameters that can be easily programmed through ...

Page 2: ...is always OFF COF Compressor OFF time with faulty probe 0 255 min time during which the compressor is OFF in case of faulty thermostat probe With COF 0 compressor is always active CH Type of action CL cooling Ht heating DISPLAY CF Temperature measurement unit C Celsius F Fahrenheit WARNING When the measurement unit is changed the SET point and the values of the parameters Hy LS US Ot ALU and ALL h...

Page 3: ...ystem ModBUS RTU compatible such as the X WEB500 3000 300 10 X REP OUTPUT OPTIONAL As optional an X REP can be connected to the instrument trough the HOY KEY connector The X REP output EXCLUDES the serial connection To connect the X REP to the instrument the following connectors must be used CAB 51F 1m CAB 52F 2m CAB 55F 5m 11 INSTALLATION AND MOUNTING Instrument XR30CX shall be mounted on vertica...

Page 4: ...uration 0 0 24 0h 0 0 Pr2 CC S Set point for continuous cycle 55 0 150 0 C 67 302 F 3 Pr2 CO n Compressor ON time with faulty probe 0 255 min 15 Pr2 CO F Compressor OFF time with faulty probe 0 255 min 30 Pr2 CH Kind of action CL cooling Ht heating cL Pr1 CF Temperature measurement unit C F C Pr2 rES Resolution in integer dE dec point dE Pr1 dLy Display temperature delay 0 20 0 min 10 sec 0 Pr2 Id...

Reviews: