37
5. Technical Specifications
5.1 Technical specifications
Model
INFOPDU600
INFOPDU800
Power
600 VA/
360 W
800 VA/
480 W
Input
Voltage
165 – 295 V
Frequency
50 / 60 Hz ±10%
Output
Voltage
220 V AC. ±10%
Switching time
2-10 ms
Form of signal
Sinusoidal from the mains /
approximated sine wave from the batteries
Protection
Fuses, protection from the
short circuit protection of the battery against overcharging
and deep discharge
Batteries
Type
Lead Acid Maintenance Free Battery
Capacity
12 V/7Ah x 1
12V/8Ah x 1
Charging time
8-10 hours
Alarm
Battery mode
Sufficient capacity of the batteries, red LED is lightning,
sound alarm once in 6 seconds
Low capacity of the batteries, red LED is lightning, sound
alarm once in 2 seconds
Batteries are discharged
Continuous sound alarm
Additionally
Work temperature
0 - 40 °С
Noise
<45 dB (1 meter)
Weight
4,5 kg
5,6 kg
Dimensions (DxHxW)
280x185x95 mm
Table 1. Technical specifications of UPS
Note: The specifications are subject to change without notice.
5.2 Battery life
Each UPS of the Info PDU series has built-in batteries, the capacity and number of
depends on the model:
INFOPDU600 – 1 x 7 Ah
INFOPDU800 – 1 x 8 Ah
Runtime graphs are below:
Summary of Contents for INFOPDU600
Page 2: ......
Page 5: ...3 Русский язык ...
Page 6: ...4 ...
Page 18: ...17 Lingua Italiana ...
Page 19: ...18 ...
Page 30: ...29 ...
Page 31: ...30 English language ...
Page 32: ...31 ...
Page 43: ......
Page 44: ......