131
13
NLS/INLS: Setting of the delay time of
UPS auto-shutdown (1 ~ 99 min),
default 1 min.
When load ≤ setting value, the system
will shut down after the configured
time.
Only in battery mode.
14
ACA/ACAUTO: AC auto-start function
selection (ON/OFF), default “ON”.
If select “OFF”, when mains power is
restored after the system was
overdischarged and shut down, the
system will not make automatic
startup.
15
DCA/DCAUTO: DC auto-start function
selection (ON/OFF)
If select “ON”, the system is in a state
of standby after the system is over
discharged and shut down. When
standby time ≥ DC auto-restart delay
time, and the charging capacity of teh
batteries ≥ 50% of the rated capacity,
the system will automatically start up
(this function is used for combined
solar system or system with external
charging equipment)
16
DCA/DCAUTO: DC auto-restart delay
time setting (0.5 H ~ 8.0 H)
That is the minimum time when the
external charger charges the batteries
after the system is over discharged
and shut down. (this function is used
for combined solar system or system
with external charging equipment)
Summary of Contents for INFORPRO1000
Page 2: ......
Page 9: ...7...
Page 10: ...8...
Page 12: ...10 3 3 1 Info Rack PRO 3 2 1 AC DC...
Page 13: ...11 3 3 1 2 3 1 3 4 3 4 1 2 15 3 4 3 5...
Page 14: ...12...
Page 16: ...14 4 2 Info Rack Pro Line Interactive IEC EN62040 1 2 1 4 3 4 3 1...
Page 17: ...15 4 3 2 4 3 3 4 3 4...
Page 18: ...16 4 4 3 4 4 1 AVR 4 4 2 4 4 3...
Page 19: ...17 4 5 4 5 1 2 3...
Page 20: ...18 4 5 2 4 5...
Page 21: ...19 4 6 4 6 1 6 1000 7 1500 3000...
Page 22: ...20 1 IEC C13 C19 6 7 2 4 6 2 1 4 1 2 3 4 6 3 USB 1 USB 8 USB...
Page 26: ...24 10 AS400 1 AS400 2 AS400...
Page 27: ...25 3 AS400 2 4 DB 9 VR 75 IF 0 15 A IF peak 4 A VDC 24 IDC 1 A 6 DB 9...
Page 29: ...27 D8 D6 D2 D8 D9 D2 D7 D8 D9 D1 D2 D8 K1 K1 8 DB 9 5 5 1 12 3 3 0 5...
Page 30: ...28 0 5 15 0 5 90 5 3 0 5 0 5 0 5 0 5 0 5 0 5...
Page 31: ...29 2 2 0 5 9 5 2 13 10...
Page 32: ...30 5 3 14 11...
Page 33: ...31 line VR batt Pow dn AVR FAULT 12...
Page 34: ...32 5 4 5 4 1 15 3 5 4 2 3 3...
Page 35: ...33 7 5 4 2 3 8 5 5 2 2...
Page 36: ...34 15 16 17...
Page 37: ...35 18 19...
Page 42: ...40 19 SAVE YES NO NO YES NO 13 6 6 1 1 2 3 6 2...
Page 43: ...41 6 3 1 15 25 C 2 6 3 4 2 5 6 8...
Page 44: ...42 8 2 30 1 2 3 4 5 6 7...
Page 45: ...43 7 4 1 SHORT 2 OUT H 3 OUT L 4 LOAD 5 RELAY 6 MOSC 7 MOST 8 SENSOR 9 TRANT AVR...
Page 46: ...44 10 INV H 11 INV L 12 SOFT AVR 13 BUS H 14 CHARGE 15 BATH 16 EOD 14...
Page 47: ...45 LOAD ON ON 3 8 LOAD 15 c...
Page 48: ...46...
Page 51: ...49 8 2 INFORPRO 20 INFORPRO1000 21 INFORPRO1500...
Page 52: ...50 22 INFORPRO2000 23 INFORPRO3000...
Page 54: ...52 9 2 batt dkc ru service_center...
Page 55: ...53 8 800 250 52 63 service dkc ru www dkc ru...
Page 56: ...54...
Page 57: ...55 Lingua Italiana...
Page 73: ...71 2 Inserire la scheda nello slot 3 Avvitare saldamente la scheda AS400...
Page 102: ...100 English language...
Page 103: ...101...
Page 143: ...141 Figure 22 Runtime graph of INFORPRO2000 UPS Figure 23 Runtime graph of INFORPRO3000 UPS...
Page 146: ...144...
Page 147: ......
Page 148: ......