Failure
Identification by
the ST LED
Recovery
Memory test failure after the
device is energized.
ST LED blinks
once in the minor
cycle.
Device goes into a reboot cycle. If the
failure persists, the device has a
hardware defect and must be replaced.
Invalid Profibus address.
ST LED blinks
twice in the minor
cycle.
Device goes into a reboot cycle. Set via
the device selector switches a Profibus
address between 1 and 126. Device will
start operating normally after the next
reboot and will be configured with a valid
address.
Illegal state in the Profibus
state machine.
ST LED blinks
three times in the
minor cycle.
Device is automatically rebooted, going
into normal operation.
Modbus communications
layer initialization error.
ST LED blinks
four times in the
minor cycle.
Device is automatically rebooted, going
into normal operation.
Insufficient number of bytes in
the input or output buffers to
store all data produced by the
rules.
ST LED blinks five
times in the minor
cycle.
Device goes into a reboot cycle until the
configuration is fixed properly.
In the compact option of the LMP-100,
check if the number of bytes produced by
input or output rules does not exceed 244
bytes, considering that 42 input bytes are
allocated if diagnostics is mapped to the
input buffer and that 16 output bytes are
allocated for the control register.
In the modular option of the LMP-100,
check if the input and output buffer sizing
is sufficient to store all data produced by
the rules.
Table 6 – Failure identification via the ST LED.