Driver output 3 configuration “Drv3Cfg”
This sets the configuration for Driver Output 3.
•
If set to
0
, no function is assigned to digital output driver 3 (pin 16 in 35 way connector)
•
If set to
1
, digital output 3
is activated if motor temperature is higher than threshold “
Temperature threshold (for output driver)
“MotTmpTh”” and deactivated when motor temperature gets l
ower
than threshold “
M3-21T Motor Temperature threshold (for output driver)
- 8 °C of hysteresis.
•
If set to
2
, digital output 3
is activated if controller temperature is higher than threshold “
output driver) “CtrTmpTh””, and deactivated when controller temper
ature gets
lower than threshold “
M3-22T Controller Temperature threshold (for
- 8 °C of
hysteresis .
•
If set to
3
, digital output 3
is activated if motor temperature is higher than threshold “
Temperature threshold (for output driver)
OR if controller temperature is higher than threshold
M3-22T Controller Temperature threshold (for
output driver) “CtrTmpTh””, whil
e it is deactivated when motor
temperature gets lower than threshold “
M3-21T Motor Temperature threshold (for output driver)
- 8 °C of hysteresis AND
controller temperature gets lower than threshold “
- 8 °C of hysteresis.
M3-20P
Motor Temperature threshold (for output driver)
“MotTmpTh”
M3-21P
Controller Temperature
threshold (for output driver) “CtrTmpTh”
These two settings represent the temperature thresholds to drive output 2 and/or 3 according to setting
Driver output 2 configuration “Drv2Cfg””
and
Driver output 3 configuration “Drv3Cfg””.
M3-22P
n/a
This setting is not active in PMS software
M3-23P
Calibration Data option
“CalValue”
Not used yet. For future development
M3-24P
Load Defaults “LoadDefs”
If this parameter is set to 1 (load defaults) all the setting in all menus will be restored to the default factory values.
This parameter requires a key cycle off-on to be effective.