SuperSigma2 AM PMS
–
V1.5.6 17-1-2020
Page 55 (97)
©2019 DMC GmbH Herten Germany
M3-17T
Accelerator supply wire off detection
”
SplyWrOf
”
This sets how the wire off detection for accelerator is detected.
•
If set to
0
, no wire off detection on accelerator potentiometer supply lines is active.
•
If set to
1
, 0V wire off detection is enabled (
of 35-Way connector).
•
If set to
2
, 5V wire off detection is enabled (
of 35-Way connector).
•
If set to
3
, both 0V and 5V wire off detection are enabled.
This parameter requires a key cycle off-on to be effective.
M3-18T
Standby timer
”
StdByDly
”
This sets a period of time after which the Line Contactor will be de-energized if there is no drive activity and the seat or
tiller switch is open.
When the seat or tiller switch is closed, the controller powers up, performs all necessary hardware and software checks
and closes the line contactor.
•
If set to
0
, then the feature is deactivated and no timer is used.
•
If set from
0.5
to
10
[minutes]
the
stand-by timer is considered and active.
M3-19T
Driver output 2 configuration “Drv2Cfg”
This sets the configuration for Driver Output 2.
•
If set to
0
, standard electro-magnetic brake function is assigned to digital output driver 2 (
o/p (Magnet Brake - Fan control)
) in 35 way connector)
•
If set to
1
, digital output 2 is activated if motor temperature is higher than threshold
Temperature threshold (for output driver)
and deactivated when motor temperature gets lower
than threshold
M3-21T Motor Temperature threshold (for output driver)
- 8 °C of hysteresis.
•
If set to
2
, digital output 2 is activated if controller temperature is higher than
threshold “
and deactivated when controller temperature gets
lower than threshold “
M3-22T Controller Temperature threshold (for
- 8 °C of
hysteresis .
•
If set to
3
, digital output 2 is activated if motor temperature is higher than threshold
Temperature threshold (for output driver)
OR if controller temperature is higher than threshold
M3-22T Controller Temperature threshold (for
output driver) “CtrTmpTh””, while it is deactivated when motor
temperature gets lower than threshold
M3-21T Motor Temperature threshold (for output driver)
- 8 °C of hysteresis AND
controller temperature gets lower than threshold “
- 8 °C of hysteresis.
M3-20T
Driver output 3 configuration “Drv3Cfg”
This sets the configuration for Driver Output 3.
•
If set to
0
, standard Power Steer function is assigned to digital output driver 3 (
(Powersteer - Fan control) in 35 way connector)
•
If set to
1
, digital output 3
is activated if motor temperature is higher than threshold “
Temperature threshold (for output driver)
“MotTmpTh”” and deactivated when motor temperature gets l
ower
than threshold “
M3-21T Motor Temperature threshold (for output driver)
- 8 °C of hysteresis.
•
If set to
2
, digital output 3
is activated if controller temperature is higher than threshold “
output driver) “CtrTmpTh””, and deactivated when controller temperature gets
lower than threshold “
M3-22T Controller Temperature threshold (for
- 8 °C of
hysteresis .
•
If set to
3
, digital output 3
is activated if motor temperature is higher than threshold “
Temperature threshold (for output driver)
OR if controller temperature is higher than threshold
M3-22T Controller Temperature threshold (for
output driver) “CtrTmpTh””, while it is deactivated when motor
temperature gets lower than threshold “
M3-21T Motor Temperature threshold (for output driver)
- 8 °C of hysteresis AND
controller temperature gets lower than threshold “
- 8 °C of hysteresis.
M3-21T
Motor Temperature threshold (for output driver)
“MotTmpTh”
M3-22T
Controller Temperature threshold (for
output driver) “CtrTmpTh”
These two settings represent the temperature thresholds to drive output 2 and/or 3 according to setting
output 2 configuration “Drv2Cfg””
and
Driver output 3 configuration “Drv3Cfg””
.