background image

LT

-1399 1.01 © 2015 Digital Monitoring P

roducts, Inc.

I n t r u s I o n   •   f I r e   •   A c c e s s   •   n e t w o r k s

2 5 0 0   N o r t h   P a r t n e r s h i p   B o u l e v a r d

8 0 0 - 6 4 1 - 4 2 8 2

w w w . d m p . c o m

s p r i n g fi e l d ,   M i s s o u r i   6 5 8 0 3 - 8 8 7 7

15305

Designed, engineered and

 

Assembled in u.s.A.

Programming/Activation

Cellular Service is required before using the 263CSMX for signal transmission. The 

263CSMX comes ready for activation with SecureCom Wireless, LLC.

1. In Remote Link panel communication programming, select Cellular Network as the 

Communication Type and select the Activate button. See Figure 4.

A. In the Activate SIM/MEID window, enter the MEID number, found on the 263CSMX 

label.

B. Select the rate plan for the 263CSMX. See Figure 5.

C. Select the Activate button at the bottom of the window.

2. After the 263CSMX is installed at the site, use a keypad and enter the 

panel's Diagnostics menu (2313).

A. Select ACTIVATE CELL by pressing a top row Select Key.

B. Press the button beneath YES on the next screen to activate the 

device.

Note:

 The ACTIVATE CELL prompt will only display if a CDMA modem 

is installed. To perform the cellular activation process from a 

keypad, the panel must be in contact with a Verizon owned tower.

Diagnostics

The panels provide a Diagnostics function to test the Communication 

integrity and Cellular Signal strength of the 263CSMX. To use Diagnostics, 

reset the panel, enter the Diagnostics code 2313 (DIAG), and press 

COMMAND.

Communication Status

Select COMM STATUS from the Diagnostics menu. The panel tests the 263CSMX for the following items.

• 263C Installed

• Cellular Tower Detected

• 263C Registered

• Communication Path Integrity

• 263C Operating

• Connect Success

• 263C Identified

Cellular Signal

Select CELL SIGNAL from the Diagnostics menu. The panel tests and indicates the strength of the signal using a bar display. One 

bar indicates a weak signal and seven bars indicate a strong signal. The signal strength is displayed as a -dBm value.

Note:

 XT Series panels display ROAM in addition to the signal strength if the communicator is not in contact with a Verizon

 

owned tower.

FCC Information

This device complies with Part 15 of the FCC Rules. Affix the included FCC label to the exterior of the panel enclosure in plain sight. Operation is 

subject to the following two conditions: 

(1) This device may not cause harmful interference, and 

(2) this device must accept any interference received, including interference that may cause undesired operation.

Changes or modifications made by the user and not expressly approved by the party responsible for compliance could void the user’s authority to 

operate the equipment.

NOTE

: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. 

These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, 

uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to 

radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause 

harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to 

try to correct the interference by one or more of the following measures:

   - Reorient or relocate the receiving antenna.

   - Increase the separation between the equipment and receiver.

   - Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

   - Consult the dealer or an experienced radio/TV technician for help.

Figure 5:  Remote Link Activation

Figure 4:  Remote Link Activation

Specifications

Primary Power  12 VDC from panel

Current Draw 

 Standby   

13mA 

Alarm   13mA

Compatibility

   XT30/XT50 Series panels

   

XR150/XR350/XR550 

Series panels

Accessories

381-2   

18" Coax Cable (included)

381-12    

12' Coax Extension

381-25    

25' Coax Extension

383 

 

Rubber Duck Antenna (included)

386 

 

Outdoor Antenna Mounting Bracket

Ordering Information

263CSMX/381-2  Cellular Communicator with 18" 

 

 

 

Coax Cable

Certifications

California State Fire Marshall (CSFM)

Cellular FCC Part 15: MIVCNN0301

Cellular Industry Canada: 4160A-CNN0301

ANSI/UL 294 

Access Control System Units 

ANSI/UL 636 

Holdup Alarm Units and System Accessory

ANSI/UL 1023 

Household Burglar

ANSI/UL 1076 

Proprietary Burglar

ANSI/UL 1610 

Central Station Burglar

ANSI/UL 1635 

Digital Burglar

ANSI/UL 985  

Household Fire Warning

ANSI/UL 864 

Fire Protective Signaling 9th Edition.

ANSI/UL365 

 Police Sta. Connected Burg Alarm Units & Systems

ANSI/UL609 

 Local Burg Alarm Units & Systems

Reviews: