XR150/XR550 Series Canadian Installation Guide
Digital Monitoring Products
11
INSTALLATION
6.8
XR150/XR550 Series Canadian Power Requirements
During AC power failure, the XR150/XR550 Series panel and all connected auxiliary devices draw their power
from the battery. All devices must be taken into consideration when calculating the battery standby capacity. The
following table lists the XR150/XR550 Series panel power requirements. You must add the additional current draw of
keypads, zone expansion modules, smoke detector output, and any other auxiliary devices used in the system for the
total current required. The total is then multiplied by the number of standby hours required to calculate the total
ampere-hours required.
Standby Battery Power Calculations
Standby Current
Alarm Current
XR150/XR550 Series Control Panel
Relay Outputs 1-2 (ON)
Switch Grounds 3-6 (ON)
Active Zones 1-8
Active Zones 9-10
2-Wire Smoke Detectors
Panel Bell Output
Qty 1 _
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______
x 174mA
30mA
5mA
1.6mA
4mA
0.1mA
174 mA
______
______
______
______
______
Qty 1 _
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______
x
217mA
30mA
5mA
2mA*
30mA
0.1mA
1500mA
217 mA
______
______
______
______
______
______mA
893A Dual Phone Line Module
Qty _______ x
12mA ______
Qty _______ x
50mA ______
263HCAN HSPA+ Cellular Communicator
Qty _______ x
24mA ______
Qty _______ x
28mA ______
277CAN Trouble Sounder Module
Qty _______ x
5mA ______
Qty _______ x
5mA ______
1100X Wireless Receiver
Qty _______ x
46mA ______
Qty _______ x
46mA ______
1100XH Wireless High Power Receiver
Qty _______ x 160mA ______
Qty _______ x
160mA ______
860 Relay Output Module (one relay active)
All four relays active
Qty _______ x
34mA
138mA
______
______
Qty _______ x
34mA
138mA
______
______
865 Style Y or Z Notification Module
Qty _______ x
26mA ______
Qty _______ x
85mA ______
866 Style W Notification Module
Qty _______ x
45mA ______
Qty _______ x
76mA ______
867 LX-Bus Style W Notification Module
Qty _______ x
30mA ______
Qty _______ x
86mA ______
869 Dual Style D Initiating Module
Qty _______ x
25mA ______
Qty _______ x
75mA ______
7060/7160 Thinline/7060A Aqualite Keypad
Qty _______ x
72mA ______
Qty _______ x
80mA ______
7063/7163 Thinline/7063A Aqualite Keypad
Qty _______ x
85mA ______
Qty _______ x
100mA ______
7070/7170 Thinline/7070A Aqualite Keypad
Active Zones (EOL Installed)
Qty _______ x
72mA
1.6mA
______
______
Qty _______
Qty _______
x
x
87mA
2mA*
______
______
7073/7173 Thinline/7073A Aqualite Keypad
Active Zones (EOL Installed)
Qty _______ x
85mA
1.6mA
______
______
Qty _______
Qty _______
x
x
100mA
2mA*
______
______
7872 Graphic Touchscreen Keypad
Active Zones (EOL Installed)
Qty _______ x 145mA
1.6mA
______
______
Qty _______
Qty _______
x
x
215mA
2mA*
______
______
7873 Graphic Touchscreen Keypad
Active Zones (EOL Installed)
Qty _______ x 143mA
1.6mA
______
______
Qty _______
Qty _______
x
x
243mA
2mA*
______
______
734 Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
Qty _______
Qty _______
x
x
15mA
1.6mA
______
______
Qty _______
Qty _______
Qty _______
x
x
x
15mA
2mA*
20mA
______
______
______
734N Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
Wiegand Reader
Qty _______
Qty _______
Qty _______
x
x
x
146mA
1.6mA
200mA
______
______
______
Qty _______
Qty _______
Qty _______
Qty _______
x
x
x
x
148mA
2mA*
20mA
200mA
______
______
______
______
734N-WiFi Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
Wiegand Reader
Qty _______
Qty _______
Qty _______
x
x
x
146mA
1.6mA
200mA
______
______
______
Qty _______
Qty _______
Qty _______
Qty _______
x
x
x
x
148mA
2mA*
20mA
200mA
______
______
______
______
Copy Sub-Totals to next page
Sub-Total Standby
*
Based on 10% of active zones in alarm.
______mA
Sub-Total Alarm ______mA