XTL Installation Guide
Digital Monitoring Products
9
InstallatIon
Listed Compliance Specifications
14.1 Introduction
The programming and installation specifications contained in this section must be completed when installing
the XTL in accordance with any of the ANSI/UL burglary standards. Additional specifications may be required
by a particular standard.
14.2 Use Marking
Commercial Central Station; Household Fire and Burglar Warning System Control Unit (Cellular)
14.3 NFPA 72
This equipment should be installed in accordance with Chapter 11 of the National Fire Alarm Code, ANSI/
NFPA 72-2002, (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269). Printed
information describing proper installation, operation, testing, maintenance, evacuation planning, and repair
service is to be provided with this equipment. Warning: Owner’s instruction notice, not to be removed by
anyone except occupant.
14.4 Types Of Service
Suitable for Central Station Standard Line Security. Suitable for Household Fire and Household Burglary. Test
weekly.
14.5 Bypass Reports
The bypass reports must be programmed as YES for all listed burglary applications.
14.6 Battery Standby
The XTL is shipped with a battery for 24 hour battery standby operation.
Household Burglar-Alarm System Units
ANSI/UL 1023
15.1 Bell Cutoff
The bell cutoff time cannot be less than four minutes.
15.2 Entry Delay
The maximum entry delay used must not be more than 45 seconds.
15.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
15.4 Wireless External Contact
When used, the External Contact of 1101 or 1102 must be programmed Normally Closed.
15.5 Wireless Supervision Time
The Zone Information Supervision Time cannot be set to 0 (zero).
15.6 Wireless Audible Annunciation
The Wireless Audible option must be selected as DAY for residential applications.
15.7 Panel location
Mount panel inside protected area.
15.8 Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.