7
MSEV Series and USHX Hardware Installation Manual Rev 1.7
Figure 2-5: Brazed access fitting
8.
Mount the USHX onto the access fitting. First, turn the USHX clockwise by hand until some
resistance is observed. Then, use a torque wrench to tighten the USHX to 70 in-lb as shown in
Figure 2-6.
Figure 2-6 USHX Installation with Torque Wrench (70 in-lb)
When torque wrench not available use 7/16” and 9/16” wrenches to tighten the
USHX as shown in Figure 2-7. Using two wrenches will ensure that the brazed joint is
not damaged during tightening.
Do NOT turn the power source ON during the installation of the wiring harness.
Figure 2-7 Installed USHX with attached 10-pin wiring harness
9.
Attach the wiring harness (10-pin connector) to the USHX as shown in Figure 2-7.
If the USHX is located in a wet or potentially wet environment, apply silicone grease
inside the 10-pin connector of the wiring harness.