Manufacturer: “DMTech” Ltd., 58 Kliment Ohridski Str., Pleven 5800, Bulgaria, EU

 http://dmtech-ltd.com

 

 

INSTRUCTION MANUAL 

CONVENTIONAL DETECTORS

 

 

D9000 series 

 

 

Type

  

Characteristics

 

Sensitivity / Class

 

D9000 SR 

Optical smoke fire detector

 

EN 54-7 

D9000 T/A1R 

Rate of rise heat detector

 

A1R, EN 54-5 

D9000 T/A1S 

Fixed temperature heat detector

 

A1S, EN 54-5 

D9000 MSR 

Combined optical smoke and heat detector

 

A1R, EN 54-5 / EN 54-7 

Caution : Read this manual before attempting to install the detector.

 

1.

 

 TECHNICAL DATA 

 

Supply voltage

 

 

 

                                              

10-30 V DC 

 

Current consumption in Standby mode

   

 

 

≤ 130 µА 

 

Current consumption in Alarm condition

 

 

 

20 mА/ 24V DC 

 

Time to enter standby mode after reset

                                         up to 35s 

 

Reset time  

 

 

 

 

 

 

2s

 

 

Degree of protection

 

 

 

                 

 

IP 43 

 

Type of the connecting line to the base

                                       0,5÷1,5 mm2 / two-wire 

 

Output in Alarm condition (term. 3) 

 

 

 

limited to 2 kΩ, negativ

 

 

Operating temperature range

 

 

                             

minus 10ºС ÷ plus 50ºС 

 

Humidity

   

 

 

                                              

(93 ± 3)% at 40ºС 

 

Dimensions with base

  

 

                   

 

 

Ø 100mm  h ≤ 52mm 

 

Weight

 

 

 

 

                                 

 

≤ 100g

 

 

2.

 

INSTALLATION 

–   

 Choose the place (according to the plans of the project) for the installation of the detector; 

 

Mount the base with appropriate fixings;

 

 

Connect the electrical cables according to the attached diagram ( Figure 1);

 

 

 

Fig.1 

 

Place the detector base and rotate clockwise till matching markers

 

 

If you want to lock detector:

 

 

Pre remove the key from the base ( Figure 2). 

 

 

Break the plastic at the specified location on the bottom of the sensor ( Figure 3 )