5.
Commissioning
5.1 Function test without configuration
DALI devices must be taught-in and assigned to groups for normal com-
missioning. This step is essential. Nevertheless, you can test the instal-
lation and operating capability of devices and the gateway in two ways
without having previously configured them:
1. By using the "Central on" and "Central off" key inputs; their wiring
configuration can be found in Section 3 “Installation” on page 6.
2. By using the menu; refer to the description in Section 5.4 “Manual
operation” on page 13.
5.2 Overview of configuration
In order to be able to make full use of all the functions of the DALI sys-
tem, the DALI gateway must be configured. This procedure is described
in detail in the following sections. The following paragraph only provides
a brief description of commissioning.
5.2.1 Required configuration steps
The following actions
must
be performed:
1. Teach-in the connected DALI devices for the DALI gateway (see Sec-
tion 5.5.3 “Repeating the teach-in for all devices” on page 19)
2. Create groups
a) Combine the devices into groups (16 groups max.) (see Sec-
tion 5.2.1 “Required configuration steps” on page 11)
b) Link the groups to a Dupline address (see Section 5.6 “Organising
lighting groups” on page 20)
5.2.2 Optional configuration steps
The following functions
may
be selected:
1. Feedback from active groups (when lighting > 0 %, see Section 5.6.2
“Creating, configuring or working on lighting groups” on page 21):
DE EN
11