The following parameters are preset when the device is delivered:

Main analysis

Frequency-selective analysis

DC

AC total

50 Hz < 100 Hz 150 Hz

100 Hz – 

1 kHz

> 1 kHz > 10 kHz

Alarm 1 300 mA 300 mA 300 mA 300 mA 300 mA 300 mA 300 mA 300 mA
Alarm 2 150 mA 150 mA 150 mA 150 mA 150 mA 150 mA 150 mA 150 mA

 

S

Thresholds when delivered 
Note: Only the alarm thresholds of the main analysis are activated.

The  LED  integrated  in  the  arc  of  the  housing  flashes,  indicating  that  the  device  is 
functioning correctly and can show the following colours:

 

»

Flashing green: IP address was successfully obtained

 

»

Orange (during commissioning): IP is being obtained via DHCP or being switched 
to the standard IP 192.168.100.100. 

 The switch to the standard IP is done for networks with no DHCP server and 

can last up to three minutes.

 

»

Orange: Threshold of alarm 2 exceeded

 

»

Red: Threshold of alarm 1 exceeded (takes priority over alarm 2)

Pressing the test key located on the side of the device results in an internal residual 
current being generated by the transformer. It is also possible to connect an external 
test key with an NO contact in parallel to the terminal strip if the transformer is not 
mounted to accessible parts of an installation. Its detection corresponds to a func

­

tion test of the analysis unit including the signal contacts.

Function of the transformer’s test button:

 

»

Press  briefly:  The  transformer  generates  an  internal  residual  current. 

  The 

potential-free contacts of the transformer also switch in this case. Its detection 
therefore corresponds to a function test of the analysis unit including the signal 

contacts.

 

»

Press and hold down (10 s): DHCP will switch back on automatically if it was pre

­

viously deactivated.

It is also possible to connect an external test button with a NO contact to the terminal 
strip if the transformer is mounted in an inaccessible part of the installation.

The  rated  current  specified  in  the  data  sheet  is  the  current  with  which  the 
DCTR  B-X  Hz-PoE  can  be  permanently  operated.  However,  different  consumers, 
such as motors, can mean that the flowing load current is temporarily several times 
higher than the rated current. As a result of physical effects in the material of the 
transformer, these inrush currents – depending on size and line structure – may in

­

correctly result in residual currents being indicated. This effect can be minimised by 
centred installation of lines routed through the transformer. If this is not possible, 
the maximum preload can be taken from the table. With the default settings of the 
DCTR B-X Hz-PoE, a current flow of six times the rated current does not lead to acti

­

vation of alarm 1 (setting: 300 mA).

Maximum preload with different load currents at 50 Hz

100 A

200 A

300 A

400 A

Symmetrical line structure

3 mA 

   6 mA

   9 mA

  12 mA

Asymmetrical line structure

9 mA

  18 mA

   27 mA

36 mA

Note: In addition, the measuring accuracy of ± 5 % of the current measuring range 

end value should be taken into account.

Example: A load current of 400 A in an asymmetrical line structure and a residual 
current of 100 MA is displayed as a maximum of 151 mA (100 mA + 36 mA + 15 mA). 

Detection ranges (automatic range switching)

Frequency

Residual current

DC

0.3 A, 3 A

50 Hz

0.3 A, 1 A, 3 A, 10 A, 30 A

< 100 Hz
150 Hz
100 Hz – 1 kHz
> 1 kHz
> 10 kHz

Installation and operating instructions

DCTR B-X Hz-PoE residual current monitors

These installation and operating instructions describe the installation 
and  commissioning  of  the  DCTR  B-X  Hz-PoE  residual  current  moni

­

tors. They are intended for use by electrically skilled persons. Electrical 
laypersons must not install and connect devices of this type due to the 
considerable potential dangers. The instructions must be kept so that 
they can be referred to at a later stage.

Scope of delivery

Operating instructions, drilling templates, ten-pin terminal strip, device, optional: 
DCTR Manager software

Warning notes

1. 

Devices with visible damage must not be installed or used.

2.  Residual current monitors of this type are not suitable as additional protection 

through  switch-off  in  combination  with  a  circuit-breaker,  for  example,  as  per 
VDE 0100 Part 410 (residual current protection).

3.  There is no distinction between operation-related leakage currents and residual 

currents.

Intended use and installation

The compact residual current monitors from the DCTR range as per DIN EN 62020 are 
used to detect and report residual currents in electrical installations, especially those 
in TN-S, TN-CS and TT networks. Use in IT networks is possible, but may be limited 
by installation regulations. DCTR B-X Hz-PoE devices are AC-DC sensitive and de

­

tect type B residual currents from DC to 100 kHz. They also meet the requirement 
for increased preventative fire safety in the detection of type B+ residual currents. 
DCTR B-X Hz-PoE devices are suitable for monitoring both AC and DC networks.

According to VDE 0100 Part 420, residual current monitors may be used in connec

­

tion with a circuit-breaker for installation switch-off in order to prevent electrical fires 
caused by insulation faults, insofar as residual current circuit-breakers are rejected 

for technical reasons.

The  devices  are  designed  for  installation  in  any  position  in  power  distributors  or 
systems in dry indoor conditions. The devices are mounted on stable surfaces or a 
mounting plate using the supplied screw points.

The following information must be observed to ensure correct operation.

Technical properties

For correct function, the DCTR B-X Hz-PoE devices require the following:

a) 

There must be a supply voltage of 24 V DC to terminals 7 and 9 or via the Ethernet 
interface with PoE. The connection of 24 V DC and PoE (48 V DC) is also possible 
at the same time in order to achieve redundancy.

b) 

The active conductors to be monitored must be fed through the inner hole of the 
sensor as symmetrically as possible. Energy may flow in either direction. The pro

­

tective conductor must not be fed through this point.

 

S

symmetrical

 

S

asymmetrical

Alternatively to b), the protective conductor can be monitored; it would then be the 
only conductor to be fed through the inner hole of the transformer.

The DCTR Manager software provides an overview of all transformers on the net

­

work and also makes it easy to manage and check residual currents. Other transform

­

ers on the network can easily be added via IP address assignment.

Residual current is reported via two integrated relays. The threshold values for these 
can be set in the DCTR Manager. The contacts of the relay can activate an external 
acoustic or visual signal. If the installation regulations allow, the relays can also effect 
the switch-off of a circuit-breaker. Furthermore, the DCTR Manager can be used to 
output and monitor the residual current via the integrated Ethernet interface.

The transformer can also be operated without software.

Frequency responses

The device has a detection range of up to 100 kHz. This is divided into seven frequen

­

cy bands that can be analysed using the DCTR Manager software. Further details can 

be found in the technical information.

It should be emphasised once again that the DCTR B-X Hz-PoE is not a measuring 
device, but a residual current monitor (RCM) as per DIN EN 62020.

Relay response times

A  response delay  can  be  set  for  each  relay  in  the  DCTR Manager  (factory  default: 

0

 ms). This prevents excessive switching in the case of a heavily fluctuating residual 

current.

Wiring diagram

1

2

3

4

5

6

7

8

9

10

 

S

ten-pin female connector

 

S

test key, Ethernet and 
service interface

The service interface is for service purposes only and cannot be used by the 
user. Both the residual current monitor and any peripheral equipment con

­

nected to it can be damaged by incorrect use.

1

2

3

4

5

6

7

8

9

10

24 V DC
  0 V DC

2

4

6

Alarm 2

1

3

5

Alarm 1

test button

 

S

Pin assignment for ten-pin female connector (de-energised)

PoE switch

DCTR Manager

PC

 

S

Wiring diagram for PoE switch and PC with DCTR Manager

Warranty 

All  professionally  installed,  unaltered  devices  are  covered  by  warranty  for  the 

 

duration of the statutory warranty period from the day of purchase by the end user. 
The  warranty  does  not  apply  to  damage  incurred  during  transport  or  caused  by 

 

short-circuit,  overloading  or  improper  use.  Should  any  defects  in  workmanship  or 
material be discovered within the warranty period, the company will provide repair 
or replacement free of charge.

DCTR Manager software

The DCTR Manager allows you to manage your transformer easily and centrally. 

 

The software also displays and documents 

 

the recorded residual currents.

Download now free of charge  
from the following link

www.doepke.de/dctr-manager

Doepke

3932180 

|

 04/2021 