background image

'EMERGENCY  SWITCH  engaged'  (labelled  ‘NOT-AUS  betätigt’)  lights  up,  and  the 
RCCB trips and cannot be switched on. If multiple DFS 4 NA devices must be oper

-

ated via an emergency switch circuit, terminals S 21 and S 22 of the devices must be 

connected in parallel. 

Troubleshooting

If  the  red  LED  for  'EMERGENCY  SWITCH  engaged'  lights  up  continuously  even 
though  the  emergency  switch  equipment  has  been  reset,  either  there  is  a  wire 
breakage,  a  contact  resistance  higher  than  3  kΩ  or  the  device  is  faulty.  To  locate 
the  specific  cause  of  the  fault,  proceed  as  follows:  Switch  the  supply  voltage  of 
the  residual  current  circuit  breaker  off  and  short-circuit  terminals  S  21  and  S  22 

 

directly on the device. If the red LED continues to light up after the supply voltage is 
reconnected, the RCCB is faulty. If the red LED no longer lights up, the cause of the 
fault lies in the system.

Warranty

All  professionally  installed,  unaltered  devices  are  covered  by  warranty  during  the 
statutory guarantee period from the day of purchase by the end user. The warranty 
is  not  applicable  to  damage  incurred  during  transport  or  caused  by  short-circuit, 
overloading  or  improper  use.  In  the  event  of  defects  in  workmanship  or  material, 
which are discovered within the warranty period, the company will provide repair or 
replacement free of charge. The warranty will be rendered null and void if the device 
is opened without authorisation.

Wiring diagram

1(N)

7(N)

3 5

8(N)

2(N) 4 6

~

S 21 S 22

Not-Aus-Kreis

emergency off circuit

 

V

Four-pole neutral conductor left or right depending on device design

rot / red

grün / green

 

V

Position and colour of LEDs. Type A RCCBs only have the red LED.

Installation and operating instructions

for residual current circuit-breakers of model range 

DFS 4 NA

This installation and operating manual is aimed at qualified electrical specialists. The 
installation of devices of this type is not appropriate for electrical laypersons due to 
the considerable potential dangers. The installation and operating manual must be 
kept so that it can be referred to at a later stage. The operator of the electrical system 
must be informed about the application and function of this protective device.

Application instructions and warnings

1.  Devices with visible damage must not be installed or used.
2.  Operation  must  only  occur  under  normal  ambient  conditions  free  of  corrosive 

gases in order to preserve the correct tripping function in the long term. Corrosive 
gases include chlorine, ammonia and sulphur.

3.  The function test with the test key is not a substitute for regular testing of the 

system.

4.  Erroneous tripping due to operation related leakage currents or atmospheric in

-

terference cannot be ruled out with absolute certainty. The consequences must 
be considered and countermeasures taken where necessary. Short-time delayed 
or selective devices and surge protection measures and system optimisations can 
provide a remedy.

5.  If the RCCB cannot be switched on, even if the consumer network is not connected 

and the emergency switch circuit is not active, the device must be replaced.

6.  The residual current circuit-breaker provides FELV (functional extra-low voltage) 

to  the  emergency  switch  circuit.  For  this  reason  the  emergency  switch  circuit 
must be rated for a voltage of 230 V AC.

Intended use and installation

DFS  4  series  protective  devices  are  residual  current  circuit-breakers  without  inte

-

grated overcurrent protection. They provide protection through automatic switch-
off in electrical systems, e.g. in accordance with VDE 0100 part 410. They meet the 
requirements for residual current protection in accordance with their characteristics 

on the rating plate.

They  are  designed  as  modular  DIN  rail  components  for  integration  in  distribution 
boards or unit housings for installation on mounting rail TS 35. Protection against 
direct contact according to protection class 2 must be ensured with the assistance of 
the associated distribution unit or device covers.

A  push-button  which  is  accessible  to  laypersons  enables  testing  of  the  switch  off 
function. An occasional test can also increase the endurance of the circuit-breaker as 
the mechanism is moved when tripped.

Installation notes

Assembly occurs by means of quick fastening on mounting rails. The connection must 

 

be made in accordance with the wiring diagram. Terminals 1, 3, 5 and 7 are used for 

 

the supply.

Testing and functional check

A  simple  function  test  with  the  assistance  of  test  key  T  must 
be 

undertaken 

following 

switching 

on 

of 

the 

mains 

volt

-

age  and  the  circuit-breaker.  When  the  key  is  pressed  the  DFS  4 

 

must  switch  off;  the  toggle  is  in  centre  position.  Resetting  to  position  '1' 
is  only  possible  if  the  toggle  has  firstly  been  moved  to  position  '0'.  The  op

-

erating  display  beneath  the  toggle  indicates  the  status  of  the  contacts: 

 

red  =  closed,  green  =  open.  This  test  must  be  carried  out  every  six  months,  as  a 
minimum, under normal operating conditions and repeated every working day for 
non-stationary systems. If tripping does not occur, the device must be replaced im

-

mediately. The operator must be informed of this. All additional tests are covered 
by  the  prescribed  inspection  test.  Tests  should  be  carried  out  according  to  DGUV 
Regulation 3 (BGV A3) depending on the location. The green LED of the AC-DC sen

-

sitive residual current circuit-breakers signals that the internal operating voltage is 
sufficient for residual current detection which is sensitive to all currents (residual cur

-

rents type A and B). If the LED does not illuminate, then only tripping via type A re

-

sidual currents is still guaranteed. The internal supply of the residual current circuit-

breaker is carried out via terminals 1, 3, 5 and 7. At least two arbitrary conductors 
must conduct AC voltage of greater than 50 V in order to guarantee residual current 
detection that is AC-DC sensitive. When an insulation test of the electrical system is 
performed using test devices in accordance with DIN EN 61557-2, the residual current 
circuit-breaker must be switched off. Performing an insulation test when the device is 
switched on or an insulation test on the side with the terminals 1, 3, 5 and 7 can lead to 
erroneous measurement values as a result of the internal adaptor.

Emergency switch equipment function

The emergency switches are connected at terminals S 21 and S 22. The emergency 
switches  must  be  implemented  as  normally  closed  contacts  so  that  switch-off  oc

-

curs in the event of wire breakage. The emergency switch equipment is ready as soon 
as the supply voltage is applied and the green LED lights up for 'operation type B' 
(labelled ‘Betrieb Typ B’). If the emergency switch circuit is open, the red LED for 

Technical data

DFS 4 NA

Rated current

16 A

25 A

40 A

63 A

Detection range 
of residual current

type A: 50 Hz, type B: 0–100 kHz

 

type B+: 0–20 kHz

Rated frequency

50 Hz

Min. 

 

operating 

voltage

for detection of 

residual currents 

type A/AC

0 V (mains independent)

for detection  

of  residual  

currents type B

50 V AC

Internal consumption

max. 3.5 W

Number of poles

four-pole

Working range of 
test equipment 
DFS 4 B NA

N left

250 V – 440 V

N right

150 V – 250 V

Dissipation power Pv (typ.)

0.2 W

0.5 W

1.3 W

3.1 W

Thermal backup fuse OCPD, 

 

utilisation category gG

1)

16 A

25 A

40 A

63 A

Short-circuit backup fuse 
SCPD, utilisation category gG

1)

100 A

Rated connection and discon-

nection capacity lm

500 A

630 A

Rated short-circuit con-
nection and disconnection 
capacity I

Δ

m

500 A

630 A

Surge current strength

Ring-wave 0.5 ms / 100 kHz: 200 A, 

 

impulse 8/20 µs: 3 kA

Shock resistance

20 g/20 ms duration

Installation position

optional

Max. operating altitude

2000 m above sea level

Input terminals

terminals 1, 3, 5, 7

Resistance to climatic 

changes

according to IEC 68-2-30: 

 

damp/heat, cyclic 

 

(25°C/55°C; 93% rel. hum., 28 cycles)

Maximum number 

 

of conductors per terminal

2 (of same type and cross-section)

Connector 
cross-section

solid

1 × 1.5 ...50 mm² (1-conductor connection),

 

2 × 1.5 ...16 mm² (2-conductor connection)

flexible

1 × 1.5 ...50 mm² (1-conductor connection),

 

2 × 1.5 ...16 mm² (2-conductor connection)

stranded

1 × 1.5 ...50 mm² (1-conductor connection),

 

2 × 1.5 ...16 mm² (2-conductor connection)

Tightening torque 

2.5 Nm to 3 Nm

Endurance

mechanical

> 5000 switching cycles

electrical

> 2000 switching cycles

Design requirements

DIN EN 61008-1, 

 

DIN EN 62423, DIN VDE 0664-120

Ambient 
temperature

standard

-25°C to 40°C

'HD' design

-25°C to 60°C

Vibration resistance

>

 5 g (f ≤ 80 Hz, duration 

>

 30 min.)

Mounting

Mounting rail in accordance with EN 60715

Housing type

distribution board installation

Housing material

thermoplastic

Protection class

IP20 (IP40 in accordance with distribution 

 

board installation)

Sealable

yes

Electromagnetic compatibility

DIN EN 61543 

Weight

approx. 510 g

Dimensions (W x H x D in mm)

81 (4.5 module width units) x 85 x 75

1) DIN VDE 0636

Additional technical data for emergency switch equipment

Connector cross-section, solid and stranded

1 x 1 mm

2

 to 1.5 mm

2

Tightening torque

max. 0.8 Nm

Output terminal for emergency switch circuit

S 21 and S 22

Type of output voltage at S 21 and S 22

FELV / 12 V in non-load operation / 

 

1 mA in short-circuit

Auxiliary contact (changeover 11, 12, 14) for 
signalling the switching status

max. 230 V AC / 6 A

 

max. 100 V DC / 1 A

Min. operating voltage for emergency switch 
equipment function

50 V AC

maximum length of emergency-off-circuit

500 m

Doepke

3930270 

|

 04/2015 

Doepke Schaltgeräte GmbH, Stellmacherstraße 11, D-26506 Norden

DE EN

Reviews: