Technical data

DMCB 2 ASA

230 V

Alternating voltage range

Activation threshold

70 V

Operating voltage range

110 V to 415 V

Max. current consumption at make-time

2 A (with 230 V)

Current flow time at max. current consumption

4.5 ms

Direct voltage range

Activation threshold

90 V

Operating voltage range

110 V to 230 V

Max. current consumption at make-time

2 A (with 230 V)

Current flow time at max. current consumption

4 ms

General

Min. pulse duration

10 ms

Electrode AC resistance

130 Ω

Duty cycle

100%

Trip time

< 20 ms

Impulse withstand voltage (1.2/50 ms)

2 kV

Circuit service life

> 4000

Protection rating

IP40 (installed)

Conductor cross-section

25 mm² to 50 mm²

Installation and operating instructions

DMCB 2 ASA operating current trip

These  installation  and  operating  instructions  are  aimed  at  electrically  skilled  per

-

sons. The installation of devices of this type is not appropriate for electrical layper

-

sons  due  to  the  considerable  potential  dangers.  These  installation  and  operating 
instructions must be retained, so that they can be referred to at a later stage.

Intended use

The DMCB 2 ASA operating current trip is a remote trip that works according to the 
operating current principle. The modular DIN rail component is designed for mount

-

ing on DIN rails for retrofitting on DMCB 2 series miniature circuit-breakers.

Warning

Devices with visible damage must not be installed or used.

Function

When  voltage  within  the  permissible  range  is  applied,  the  operating  current  trip 
activates immediately and trips the internally connected DMCB 2 miniature circuit-
breaker. After a trip the DMCB 2 ASA also interrupts the supply to its own magnetic 
trip coil, thus preventing the tripping device from experiencing a thermal overload in 
the event of continuous trip commands. The switch levers of the DMCB 2 ASA operat

-

ing current trip and of the DMCB 2 series miniature circuit-breaker are mechanically 
coupled, so that the toggle of the DMCB 2 is included when switching on and off. If the 
DMCB 2 is manually switched off, the DMCB 2 ASA trips mechanically even without a 
control voltage. In the event of an electrical trip of the DMCB 2, the DMCB 2 ASA also 
trips mechanically internally. The trip-free mechanism of the DMCB 2 ASA ensure 
safe function if the toggle is mechanically hindered. 

Mounting

The operating current trip must always be mounted by sliding it to the left on the 
DMCB 2 miniature circuit-breaker on a DIN rail. The trip is removed by sliding it to the 
right. The connection must be made in accordance with the wiring diagram.

ASA 1

DMCB 2

DMCB 2

Warranty

All  professionally  installed,  unaltered  devices  are  covered  by  warranty  during  the 
statutory warranty period from the day of purchase by the end user. The warranty 
is  not  applicable  to  damage  incurred  during  transport  or  caused  by  short-circuit, 
overloading  or  improper  use.  In  the  event  of  defects  in  workmanship  or  material, 
which are discovered within the warranty period, the company will provide repair or 
replacement free of charge. The warranty will be rendered null and void if the device 
is opened without authorisation.

Wiring diagram

1

2

Doepke

3932167 

|