Installation and Operating Manual

for DRCBO 4 Hi 1

This installation and operating manual is aimed at qualified electrical specialists. The 
installation of devices of this type is not appropriate for electrical laypersons due to 
the considerable potential dangers. The installation and operating manual must be 
kept so that it can be referred to at a later stage.

Application instructions and warnings

1.

Devices with visible damage must not be installed or used.

2.

When removing the opening, no parts of the housing should fall inside the device. 

3. This auxiliary switch is designed exclusively for RCBOs of the DRCBO 4 series as well 

as the FIB and FIC series, in Type A 3+N and Type B versions.

Intended use and mounting
The  DRCBO  4  Hi  1  auxiliary  switch  is  suitable  for  installation  on  residual  current 
circuit-breakers with integral overcurrent protection. It can be used as an auxiliary 
switch or as a signal switch. It should be installed to the left of the RCBO, once you 
have removed the plastic cut-out (see Fig. 1).  Move the RCBO's toggle and auxiliary 
switch to the ON position. After moving the auxiliary switch, turn the locking screws 
90° to the right (see Fig. 2).

Selectable setting
Using the selector switch (see Fig. 3), you can select either the auxiliary switch or the 
signal switch function:

a)  Auxiliary switch: horizontal position

The  auxiliary  switch  function  is  used  to  display  the  switch  position  of  the  
switching mechanism.

b)  Signal switch: vertical position

The signal switch function is used to display any RCBO trips caused by
overcurrent or residual current.

In order to switch from the signal switch function into the auxiliary switch function, 
press the selector switch from the vertical position and then turn 90° to the right.  
In order to switch from the horizontal position (auxiliary switch function) to the verti-
cal position, turn the selector switch 90° to the right.

Test key
To test the auxiliary switch's function, press the test key (see Fig. 3). The auxiliary 
switch is fitted with a grey indicator; wich is indicating the position of the switching 
mechanism. Press the indicator to activate the switching mechanism. This makes it 
possible to check whether the auxiliary switch is connected correctly, without having 
to switch on the RCBO to do so.

Warranty
All professionally installed, unaltered devices are covered by warranty during the 
statutory guarantee period from the day of purchase by the end user. The warranty is 
not applicable to damage incurred during transport or caused by short-circuit, over-
loading or improper use. In the event of defects in workmanship or material being dis-
covered within the warranty period, the company will provide a repair or replacement 
free of charge. The warranty will be rendered null and void if the device is opened 
without authorisation.

Technical Data

DRCBO 4 Hi 1

Rated voltage

230 V AC

Rated current

AC12 230 V

6 A

AC13 230 V

3 A

DC12 110 V

1 A

DC45 48 V

2 A

DC12 24 V

4 A

Rated short-circuit current

1 kA (gG 6 A)

Type of contact

Changeover contact

Protection class

IP 20

Dimensions

W 8.75 mm (0.5 HP) × H 92 mm × D 69.4 mm

Product standard

EN 62019

Doepke

3930266 | 11/2014 | Doepke Schaltgeräte GmbH, Stellmacherstraße 11, D-26506 Norden