48
999808702 - 11/2019
General
User Information
Load-bearing tower Staxo
100
eco
Shoring to the superstructure
For transferring
planned horizontal loads
e.g. wind
loads, concrete loads or in custom applications (e.g. on
inclined load-bearing towers or for high load-bearing
capacities).
H ... Horizontal force
V ... Resulting vertical force from H
A ... Back-stay/shoring force
Follow the manufacturer's applicable fitting instruc-
tions.
Permitted load-bearing capacity of Eurex 60
550 (compressive force)*
Used as a plumbing accessory
* 15
kN tensile force at any extension length
30
kN tensile force at any extension length and when anchored with
2 dowels
Temporary back-stays directly on the
load-bearing tower, for site-erection
A
Load-bearing tower
B
Plumbing strut Eurex 60 550
C
Plumbing strut shoe Eurex 60 EB
D
Prop head Eurex 60 Top50
Required load-bearing capacity of the dowels
used:
R
d
≥ 25.5
kN (R
perm.
≥ 17
kN) in any direction when 2
dowels are used.
CAUTION
➤
The plumbing strut must not be dismounted
until it is certain that there is sufficient stabil-
ity for the load-bearing tower.
A
V
98087-228-01
H
A
B
D
C
Permitted load-bearing capacity [kN]
Extension length [m]
For more detailed information, see the 'User
Information booklet Eurex 60 550'
NOTICE
Only suitable for use during erection of the
load-bearing tower, but
not
for transferring
planned horizontal loads.
A
Scaffolding tube 48.3mm (with drilled hole
⌀
17mm)
B
Normal coupler 48mm
C
Spindle connecting plate T
D
Back-stay for load-bearing towers
E
Tie-rod 15.0mm
3
4
5
6
7
8
9
10
13
14
35
30
25
20
15
10
5
0
11
12
9745-101
A
C
B
E
D
98087-233-01