24
24
2.3
Safety function of the module
Both safety signals of a safety module must be switched off (contact open) and switched
on within 250 ms (contact closed) to be recognised as safe. Both control contacts of the
charger must go into active state within 3 sec.
If the BI 5910 is switched off while the remote control is active, e.g. by activating a hardwired
e-stop button, the red e-stop button of the remote control has to be pressed also in order
to reset the BI 5910. This avoids activation of the machine by a second person while a
person with active remote control is inside a dangerous area.
2.3
Safety function of the module
Both safety signals of a safety module must be switched off (contact open) and switched
on within 250 ms (contact closed) to be recognised as safe. Both control contacts of the
charger must go into active state within 3 sec.
If the BI 5910 is switched off while the remote control is active, e.g. by activating a hardwired
e-stop button, the red e-stop button of the remote control has to be pressed also in order
to reset the BI 5910. This avoids activation of the machine by a second person while a
person with active remote control is inside a dangerous area.