Status Indicator

Indication of System Errors

These errors are indicated by flashing codes of the white LEDs Run 1 
and/or Run 2. The green LEDs and all outputs turn inactive. The system 
will only restart after the supply voltage has been switched off and on 
again. 

Error codes*

0) 

(both white LEDs are off): 

 

Another input module indicates a system error.

1)  

To 4): not used

5) 

Incorrect setting of function:

 

- The rotary switches for channel 1 and 2 has different or 

 

   incorrect positions

 

- The setting of the 4 upper Dip-switches (channel 1) are not 

 

  identically to the 4 lower Dip-switches (channel 2)

6) 

LED Run 1 flashes: Undervoltage

 

LED Run 2 flashes: Overvoltage

7), 8) Not used
9) 

Connection error between the input modules

 

No terminating connector available.

 

·  Control or input module defective

10), 11), 12), 13) a. 14) Internal errors

* number of short flashing impulses, followed by a longer space

Function errors are indicated by the white LED Run 1 and by the output 
48. During this time, the white LED Run 2 remains on. Output 58 remains 
on as long as the error is pending; it flashes regularly while waiting for the 
assigned start signal.

Error codes*

1)  First Emergency stop contact open
2)  Second Emergency stop contact open
3)  Stop contact open
4)  Error start input
5)  Input error (interruption or short-circuit)
6)  Output error at the safety output of the control unit or at the safety 

outputs of the extension modules (feedback loop interrupted, assigned 
output module does not exist).

7)  Error at the twin contacts of the Emergency stop button

* number of short flashing impulses, followed by a longer space

In case of error 5) and 6), the LEDs Run 1 and the outputs 48 to 58 of 
the inputs modules which permit activation of the safety outputs flash 
fast and regularly until the error is remedied and acknowledged by a start 
signal assigned to the control unit.

Indication of Function Errors

Permanently OFF

Pulsing

Permanent ON

Output

48

all relays inactive 

due to system error

Function error

Activation of the 

assigned safety 

outputs is 

permissible

LED

run 1

all relays inactive

due to system error

Function error when 

LED Run 2 is ON, or

system error when

LED Run 2 is OFF

or flashing

Activation of

the assigned

safety outputs  

is permissible

Output

58

Activation of the 

assigned safety

outputs is permissib-

le or system error

Waiting for

start signal

Function error

LED

run 2

all relays inactive   

due to system error

all relays inactive 

due to system error

No system error

Summary of Contents for SAFEMASTER M BH 5911

Page 1: ...A1 A1 S11 S12 S13 S14 T1 X11 X11 X12 X12 T2 T3 T4 Y1 Y2 A1 A2 33 23 13 34 24 14 BH 5911 03 Circuit Diagrams X11 A1 S11 11 S13 23 X12 33 X11 A2 T1 12 T3 24 X12 34 S14 48 58 S12 Y1 T2 Y2 T4 M8744 48 58...

Page 2: ...several start inputs may be assigned to one module plate M2929 M9039_b 0 0 1 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 2 2 3 4 output start input Mod3 T1 Mod2 T2 Mod1 T3 Base T4 Mod3 T1 Mod2 T2 Mod1 T3 Base T4...

Page 3: ...Error codes 1 First Emergency stop contact open 2 Second Emergency stop contact open 3 Stop contact open 4 Error start input 5 Input error interruption or short circuit 6 Output error at the safety ou...

Page 4: ...11 S13 S14 X12 emergency stop 13 23 33 34 24 14 58 48 waiting for start error error indication enabling active K1 K2 machine enabling M9047_a X11 T4 T3 T2 T1 T1 T2 T3 T4 X12 L L A1 A2 Y1 X11 Y2 S12 S1...

Page 5: ...T1 T2 T3 T4 X12 LC waiting for start error error indication enabling active machine enabling trans mitter OSSD BH5911 L L L A1 A1 A2 A2 Y1 Y1 X11 X11 Y2 Y2 S12 S12 S11 S11 S13 S13 S14 S14 X12 X12 13 1...

Page 6: ...1 T1 T2 T2 T3 T3 T4 T4 X12 X12 T1 stop T2 T3 T2 T3 emergency stop waiting for start error waiting for start error error indication enabling active error indication enabling active machine enabling mac...

Page 7: ...for arc free operation Switching of small loads 100 mV Thermal current Ith max 5 A see quadratic total current limit curve Switching capacity to AC 15 NO contact 3 A AC 230 V IEC EN 60 947 5 1 NC con...

Page 8: ...year hop 24 h d hours day tZyklus 3600 s Zyklus 1 h hour Values according to IEC EN 62061 IEC EN 61508 SIL CL 3 IEC EN 62061 SIL 3 IEC EN 61508 HFT 1 DCavg 98 3 SFF 99 6 PFHD 4 06E 10 h 1 Safety Rela...

Reviews: