Technical Data

 Characteristics

Limit curve for arc-free operation

Switching current I

Switching

voltag

e

U

[

V]

safe breaking, no continuous arcing
under the curve, max. 1 switching cycle/s

[A]

0

50

100

200

250

150

1

2

3

4

5

6

7

8

M7073_

a

Quadratic total current limit curve

Vibration resistance:

 

Amplitude 0.35 mm

 

Frequency 10 ... 55 Hz,  IEC/EN 60 068-2-6

Shock resistance:

 

Acceleration: 

10 g

Pulse duration: 

16 ms

Number of shocks: 

1000 per axis on three axes

Climate resistance:

 

0 / 050 / 04 

IEC/EN 60 068-1

Terminal designation:

 

 

               EN 50 005

Wire connection:

 

1 x 2.5 mm

2

 stranded wire with sleeve, or

 

1 x 4 mm

2

 massive, or

 

2 x 1.5 mm

2

 stranded wire with sleeve

 

DIN 46 228-1/-2/-3/-4

Wire fixing:

 

Plus-minus terminal screws M3,5 

 

box terminals with wire protection

Surge supression: 

 

When connecting inductive loads to the

   

relay outputs (contactor coils, valves, 

   

electric brakes) surge supressor elements 

   

like diods, capacitros, RC combinations, 

   

etc. have to be connected directly to the 

   

connection terminals of the controlled

   

devices, keeping the connection wires 

   

as short as possible.

Mounting:

 

DIN rail 

               IEC/EN 60 715

Dimensions

Width x height x depth:

 

45 x 84 x 121 mm

Safety Related Data for E-STOP

Values according to EN ISO 13849-1:

Category: 4

PL: e

MTTF

d

193.3 a

DC

avg

98.3  

%

d

op

365 

d/a (days/year)

h

op

24 

h/d (hours/day)

t

Zyklus

3600 s/Zyklus

  

=

 1 

/h (hour)

Values according to IEC EN 62061 / IEC EN 61508:

SIL CL: 

IEC EN 62061

SIL 

IEC EN

 

61508

HFT

*)

: 1

DC

avg

98.3  

%

SFF 

99.6 %

PFH

D

4.06E-10 h

-1

Safety Related Data for light curtains ,safety gates or two-hand

Values according to EN ISO 13849-1:

Categorie: 4

PL: e

MTTF

d

30.4 a

DC

avg

99.0  

%

d

op

220 

d/a (days/year)

h

op

12 

h/d (hours/day)

t

Zyklus

138 s/Zyklus

Values according to IEC/EN 62061 / IEC/EN 61508:

SIL CL: 

IEC/EN 62061

SIL 

IEC/EN 61508

HFT

*)

: 1

DC

avg

99.0  

%

SFF 

99.6 %

PFH

D

7.91E-09 h

-1

*

)

 HFT = Hardware-Failure Tolerance

nfo

The values stated above are valid for the standard type.
Safety data for other variants are available on request.
The safety relevant data of the complete system has to be 
determined by the manufacturer of the system.

 

Ordering Example

BH 5911.03/00MF0 DC24V 

3 NO contacts

BH 5911.22/00MF0 DC24V 

2 NO contacts, 1 NC contact

 CSA-Data

Wire connection: 

60°C / 75°C copper conductors only

   

AWG 20 - 12 Sol Torque 0.8 Nm

   

AWG 20 - 14 Str Torque 0.8 Nm

nfo

Technical data that is not stated in the CSA-Data, can be found 

in the technical data section.

 CCC-Data

Thermal current I

th

4 A

Switching capacity

to AC 15: 

3 A / AC 230 V   

IEC/EN 60 947-5-1

to DC 13: 

1 A / DC 24 V    

IEC/EN 60 947-5-1

nfo

Technical data that is not stated in the CCC-Data, can be found 

in the technical data section.

E. DOLD & SÖHNE KG • D-78114 Furtwangen

e-mail: dold-relays@dold.com • internet: http://www.dold.com

• 

PO Box 1251 • Telephone (+49) 77 23 / 654-0 • Telefax (+49) 77 23 / 654-356

Summary of Contents for SAFEMASTER M BH 5911

Page 1: ...A1 A1 S11 S12 S13 S14 T1 X11 X11 X12 X12 T2 T3 T4 Y1 Y2 A1 A2 33 23 13 34 24 14 BH 5911 03 Circuit Diagrams X11 A1 S11 11 S13 23 X12 33 X11 A2 T1 12 T3 24 X12 34 S14 48 58 S12 Y1 T2 Y2 T4 M8744 48 58...

Page 2: ...several start inputs may be assigned to one module plate M2929 M9039_b 0 0 1 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 2 2 3 4 output start input Mod3 T1 Mod2 T2 Mod1 T3 Base T4 Mod3 T1 Mod2 T2 Mod1 T3 Base T4...

Page 3: ...Error codes 1 First Emergency stop contact open 2 Second Emergency stop contact open 3 Stop contact open 4 Error start input 5 Input error interruption or short circuit 6 Output error at the safety ou...

Page 4: ...11 S13 S14 X12 emergency stop 13 23 33 34 24 14 58 48 waiting for start error error indication enabling active K1 K2 machine enabling M9047_a X11 T4 T3 T2 T1 T1 T2 T3 T4 X12 L L A1 A2 Y1 X11 Y2 S12 S1...

Page 5: ...T1 T2 T3 T4 X12 LC waiting for start error error indication enabling active machine enabling trans mitter OSSD BH5911 L L L A1 A1 A2 A2 Y1 Y1 X11 X11 Y2 Y2 S12 S12 S11 S11 S13 S13 S14 S14 X12 X12 13 1...

Page 6: ...1 T1 T2 T2 T3 T3 T4 T4 X12 X12 T1 stop T2 T3 T2 T3 emergency stop waiting for start error waiting for start error error indication enabling active error indication enabling active machine enabling mac...

Page 7: ...for arc free operation Switching of small loads 100 mV Thermal current Ith max 5 A see quadratic total current limit curve Switching capacity to AC 15 NO contact 3 A AC 230 V IEC EN 60 947 5 1 NC con...

Page 8: ...year hop 24 h d hours day tZyklus 3600 s Zyklus 1 h hour Values according to IEC EN 62061 IEC EN 61508 SIL CL 3 IEC EN 62061 SIL 3 IEC EN 61508 HFT 1 DCavg 98 3 SFF 99 6 PFHD 4 06E 10 h 1 Safety Rela...

Reviews: