2

11.01.21 en / 335A

The unit needs a connected auxiliary supply.
It is designed for single phase AC/DC measurement.

The LED indicate the state.

Green: 

On, when auxiliary voltage present

Orange (flashes): 

No measurement;  

 

unit in input mode

Red (short On, short Off): 

Failure overvoltage

If the measured value is higher then the upper end of scale value, the 
display shows the fault message "OL"

The Device is programmable for AC- or DC- measuring. 
On AC-measurement the rectified mean value is measured. 
On sinusoidal input signals the RMS value is  displayed. 

After connecting the auxiliary supply to terminals A1-A2 the startup delay 
disables the monitoring function so that changes on the input have no 
influence on the relay output of the VARIMETER. 
The device is in display (RUN) mode and continuously measures the actu-
al values. Pressing  

Esc

 for more than 3 sec starts the input mode.

If the setting value is exceeded the relay switches and the display indica-
tes this state. The display is inverted, flashes and shows the error.

The fault memory is selectable 
With button 

 the fault memory can be deleted.

On the unit MH 9064it is possible to assign different functions to the diffe-
rent relays so one can be used as pre-warning and the other as alarm out-
put. Relay output 1 switches when actual value exceeds the pre-warning 
setting. If a second setting assigned to relay output 2 the unit gives an 
Alarm signal.

M11095

e

f

Display “Rel.2” active

Display “Rel.1” active

Selection of
Functions / Setting and
measuring values

Change to setup mode (3...6s)

Change to Run mode (3...6s)

LED status indication

Error memory 1 active

Error memory 2 active

Active manual reset
Manual reset activated: flashes when me-
mory mode is ON and relay in failure state.
Reset with button "

"

Contact state of the output relays

Function

Functional Notes

Setting

Indicators

Cursor LCD Display