Display (Run) - Mode

Input-Mode

 UP  /  

 DOWN

After power up the relay is in display (Run) mode. 

The measurement is interrupted, the relays are in failure state and the 
indicator LED has orange color

 

 

 Buttons have no function

 

 

 Selection of parameters and setting of thresholds

 ENTER

Manual reset, when manual reset is selected for output relay

- Shifts cursor to the right

Reset works only when fault is removed

- Saves the value no-voltage safe
- Pressing for more than 3 sec: Change to display (Run) mode.

Esc

 Esc

- Pressing for more than 3 sec: Change to input mode

- Shifts cursor to the left
- Leave setting without saving

LCD-Display

   

Rel.1 Rel.2 Sp1 Sp2

Rel.1 Rel.2 Sp1 Sp2

<U

Rel.1 Rel.2 Sp1 Sp2

>U

Rel.1 Rel.2 Sp1 Sp2

<U

Setting Parameter

< U        Fault, when value drops under set point
> U        Fault, when value exceeds set point
OFF       Measurement disabled

If the adjusted threshold of at least one measuring function is exceeded, the corresponding relay output switches after the selected time delay tv and 
the fault is indicated on the display.

Manual reset can be activated or de-activated and is operated with 

 on the unit.

Limit values for Rel.1 and Rel.2
Selectable with buttons  

 

 

.

Factory 

setting

<U:

Response value undervoltage  
(Undervoltage relay)

OFF

>U:

Response value overvoltage,,  
(Overvoltage relay)

*

Hyst: response value hysteresis

5 %

t

v

:

On delay for relays  ( 0 ... 10 sec )

0 s

A / R: Seting open- / closed circuit operation

R

Sp:

Error storage ( ON / OFF )

OFF

Response values can be deactivated. (OFF)
*) dependent to device-variant (measuring range)

Selectable with buttons  

 

 

.

Factory 

setting

t

a

:

Start up delay, when auxiliary voltage connected 
( 0.2 ... 10 s)

0.2 s

AC/DC Measuring voltage AC or DC

AC

(Restore factory settings)
Before auxiliary voltage connected press button 

Esc

 .

During start press and hold.

The switching mode energized or de-energized on trip can be set in input 
mode. The MH 9064 has 2 relay outputs. Monitoring function can be assig-
ned to Relay 1 and/or to Relay 2.

Operating

Adjustable Parameter

Further Setting Parameter

Restore Factory Settings

Indicator output