Assembling the device
90
Setting DIP switches on the devices
ATTENTION!
Functional problems by actuating the DIP switches with
voltage applied.
Only actuate the DIP switches on the device in a dead-
voltage state.
Make sure that DIP switches (1) 1 and 2 on the control unit and the external
reader are in the ON position.
Schematic diagram of ENiQ Module Reader/Module Reader Terminal
Connecting the Access Manager or Access Manager Terminal Compact
(control unit) to the network
ATTENTION!
Property damage through incorrect connection.
Only carry out the network connection.
Do not connect the voltage supply via PoE (Power over
Ethernet) yet.
Make sure that the cable pairs for Ethernet RD and TD remain twisted up to
the terminal on the DOM device.
Data is generally transferred at terminals 11 to 14.
If a PoE "End-Span Device" (PoE switch) is used, both data transfer and
energy supply is carried out on the data lines at terminals 1 to 4 (wires 1, 2, 3,
6). However, you can still connect wires 4, 5, 7 and 8 to terminals 5 and 6 for
insulation if they are not used for any other purpose in your network wiring.