UC120 is a communicative room heating controller with one binary input and one 
0...10  V  DC  output  for  control  of  a  radiator  or  electrical  heater.  It  can  work 
autonomously,  or  in  connection  to  a  primary  controller  (MiniPLC  or  SoftPLC),  or 
building management system (RcWare Vision or any SCADA). 
 

Application 
 
 

 

Systems  with  radiators,  electric  heaters,  or  floor  heating 

  control  and 

measuring of room temperature 

 

monitoring and communication of room temperatures 
 

Function 
 
 

The  controller  reads  actual  room  temperature,  setpoint  shift  by  a  knob,  and  set 
operation  status  which  is  set  by  short  push  of  the  knob.  The  room  temperature  is 
measured in the range of -20 to +50 

°C. Measured and set values are processed in a PI 

algorithm, brought to one 0..10 V DC output. All values are displayed on a large LCD 
display. 
 
The functionality and control parameters, i.e. P and I constants, and hysteresis, can be 
set  with 

ModComTool

,  the  configuration  software,  which  is  free  to  download  at 

http://domat-int.com/en/downloads/software

. 

 
The controller contains real time clock with a weekly scheduler (6 events per day). It 
changes between three operation modes: Day, Night, and Off. A short push in the Night 
mode switches to Party mode 

 Comfort extension by 2 hours. 

 
The Change-over function (communicated over the bus) switches to the cooling mode 
while  cooling setpoints come  into effect. This mode  is used when  heat pumps with 
change-over mode are installed. The change-over signal is read from the heat pump 
interface  or  a  thermostat  at  the  supply  water  piping,  and  is  transmitted  to  the 
controllers  over  MiniPLC,  UCWEB,  or  any  Modbus  master.  See 

Room  units  and 

controllers, Communication protocol description

 handbook for register addressing and 

communication examples. 
 

Summary of Contents for UC120

Page 1: ...gorithm brought to one 0 10 V DC output All values are displayed on a large LCD display The functionality and control parameters i e P and I constants and hysteresis can be set with ModComTool the configuration software which is free to download at http domat int com en downloads software The controller contains real time clock with a weekly scheduler 6 events per day It changes between three oper...

Page 2: ...current Resolution 1x 0 10 V DC 10 mA corresponding to 1 kOhm load 50 mA tolerant to permanent short circuit 10 bit D A converter Setpoint correction according to configuration 10 to 1 K Communication RS485 separation Baud rate 2 wire RS485 Modbus RTU slave optically separated up to 1000 V selectable 1200 9600 115200 bps Display LCD 60 x 60 mm Terminals screw terminals for 0 14 1 5 mm2 wires Cover...

Page 3: ...erator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At the back of the bottom there is an aperture for cabling The bottom should be installed and cabling connected first and the upper part inserted after the construct...

Page 4: ...m the event selection Turn the knob to select the operation mode Day Night Off Event inactive invoked by this event If the event is not active the operation mode is not changed at the set time Short push to confirm the operation mode setting The event time displays Turn the knob to set the time of the event and confirm by a short push Then turn the knob to select another event or long push and tur...

Page 5: ...sted value by a short push Turn knob to change value Confirm by a short push again If there is no user activity for 30 s the controller goes to the basic display mode Default values The default values as well as all other settings PI parameters address baudrate can be set by the configuration program ModComTool Dimensions All dimensions in mm ...

Page 6: ... Belden 8205 cable A terminal is designed for maximum 3 wires of 0 8 mm2 Temperature compensation After switching the unit on allow about 90 mins to dissipate the heat inside of the housing Then the sensor is measuring correctly Do not change the sensor correction variable immediately after powering the device on RoHS notice The device contains a non rechargeable battery which backups the real tim...

Page 7: ... versions 08 2016 Changed reference to the configuration software Added picture and description of the installation and link on the datasheet with other colours 03 2017 Added picture and description of the installation and link on the datasheet with other colours ...

Reviews: