background image

 

domat UC220 

03/2017 Subject to technical changes. 

 

 

 

UC220 

Communicative heating and 
cooling controller, 0..10 V output 

 

 

 

 

 

 

 

Summary 
 

UC220 is a communicative room heating controller with two binary inputs and two 
0...10 V DC outputs for control of a radiator or electrical heater and a cooling valve 
(cooling panels, chilled ceilings). It can work autonomously, or in connection to a 
primary controller (MiniPLC or SoftPLC), or building management system (RcWare 
Vision or any SCADA). 

 

Application  

 

Systems  with  radiators,  electric  heaters,  or  floor  heating,  and  chilled 
ceilings or panels – control and measuring of room temperature 

 

monitoring and communication of room temperatures 

 

Function 
 
 

The  controller  reads  actual  room  temperature,  setpoint  shift  by  a  knob,  and  set 
operation  status  which  is  set  by  short  push  of  the  knob.  The  room  temperature  is 
measured in the range of -20 to +70 °C. Measured and set values are processed in a PI 
algorithm, which is brought to sequence block and two 0..10 V DC outputs. All values 
are displayed on a large LCD display. 
 
The functionality and control parameters, i.e. P and I constants, and hysteresis, can be 
set  with  ModComTool,  the  configuration  software,  which  is  free  to  download  at 

http://domat-int.com/en/downloads/software

. 

 
The controller contains real time clock with a weekly scheduler (6 events per day). It 
changes between three operation modes: Day, Night, and Off. A short push in the Night 
mode switches to Party mode – Comfort extension by 2 hours. 
 
The digital inputs read signals from a window contact and presence sensors. They can 
be used optionally. 
 
The communication bus is Modbus RTU over RS485, therefore the controllers are easily 
to  integrate  into  any  SCADA  or  BMS  system.  Protocol  description  is  available  in  a 
separate document. 

Summary of Contents for UC220

Page 1: ...s set by short push of the knob The room temperature is measured in the range of 20 to 70 C Measured and set values are processed in a PI algorithm which is brought to sequence block and two 0 10 V DC outputs All values are displayed on a large LCD display The functionality and control parameters i e P and I constants and hysteresis can be set with ModComTool the configuration software which is fr...

Page 2: ...nt correction according to configuration 10 to 1 K Communication RS485 separation Baud rate 2 wire RS485 Modbus RTU slave optically separated up to 1000 V selectable 1200 9600 115200 bps Display LCD 60 x 60 mm Terminals screw terminals for 0 14 1 5 mm2 wires Cover ABS RAL9010 other colours Weight 0 13 kg Dimensions see below Terminals 1 2 3 4 5 6 7 8 9 Terminals as seen from above in the bottom pa...

Page 3: ...sure correct values of temperature i e in the height of about 150 cm with no direct sunlight or other heat cool source AHU outlets refridgerator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At the back of the bottom t...

Page 4: ...he weekday 1 to 7 Then short push to confirm the selection Turn the knob to select the event large number 1 to 6 Each event displays the mode activated by this event Short push to confirm the event selection Turn the knob to select the operation mode Day Night Off Event inactive invoked by this event If the event is not active the operation mode is not changed at the set time Short push to confirm...

Page 5: ... are flashing Setpoint temp Cooling Off mode Temperature Cooling Empty house are flashing Select the requested value by a short push Turn knob to change value Confirm by a short push again If there is no user activity for 30 secs the controller goes to the basic display mode Default values The default values as well as all other settings PI parameters address baud rate can be set by the configurat...

Page 6: ...5 cable A terminal is designed for maximum 3 wires of 0 8 mm2 Temperature compensation After switching the unit on allow about 90 mins to dissipate the heat inside of the housing Then the sensor is measuring correctly Do not change the sensor correction variable immediately after powering the device on RoHS notice The device contains a non rechargeable battery which backups the real time clock and...

Page 7: ...to technical changes 7 Changes in versions 09 2016 Changed reference to the configuration software and deleted Related products 03 2017 Added picture and description of the installation and link on the datasheet with other colours ...