domat US100 

05/2018 Subject to technical changes.. 

 

 

 

US100 

Communicative heating controller 
with sunblind control 

 

 

 

 

 

 

Summary  

US100  is  a  communicative  room  heating  controller  with  one  PWM output  for 
control of  a  radiator  or  electrical  heater,  and  two  digital  outputs  for  sunblind 
motor  control.  It  can  work  autonomously,  or  in  connection  to  a  primary 
controller (MiniPLC or SoftPLC), or to a building management system (RcWare 
Vision or any SCADA). 
 

Application 
 

 

Systems  with  radiators,  or  electric  heaters 

  control  and  measuring  of 

room temperature, sunblind manual control and central override 

 

monitoring and communication of room temperatures 
 

Function  

The controller reads actual room temperature, setpoint set by the pusbuttons, and set 
operation  status  which  is  set  by  short  push  of  the  central  button.  The  room 
temperature is measured in the range of -20 to +50 

°C. Measured and set values are 

processed in a PI algorithm, at the output of which there is a PWM controlled triac. All 
values are displayed on a large LCD display. 
 
The output works either as PWM controlled by a PI controller, or on/off (thermostat). 
The functionality and control parameters, i.e. P and I constants, and hysteresis, can be 
set  with 

ModComTool

,  the  configuration  software,  which  is  free  to  download  at 

http://domat-int.com/en/downloads/software

. 

 
The digital input may be configured as a window contact (switches to Off) or presence 
contact  (switches  to  Standby/Night).  It  may  be  set  as  normally  open  or  normally 
closed. 
 

The sunblinds are controlled by the „up“ and „down“ buttons. It is possible to control 
the sunblind operation as central building function, such as „fully closed“ at n

ight time, 

„fully open“ at strong wind, etc. Those commands must be programmed in the BMS 

and communicated over the RS485 bus to the controller. 
 

Summary of Contents for US100

Page 1: ...l button The room temperature is measured in the range of 20 to 50 C Measured and set values are processed in a PI algorithm at the output of which there is a PWM controlled triac All values are displayed on a large LCD display The output works either as PWM controlled by a PI controller or on off thermostat The functionality and control parameters i e P and I constants and hysteresis can be set w...

Page 2: ...essing and communication examples The communication bus is Modbus RTU over RS485 therefore the controllers are easily to integrate into any SCADA or BMS system Technical data Power 24 V AC 10 Consumption 1 5 W peripherials ca 5VA Measuring range 20 50 C Protection IP20 Sensor accuracy according to DIN IEC 751 Class B Output heating 1x solid state relay zero switching for AC load 24 V AC against G0...

Page 3: ...ller into default state and sets bus address to 1 baud rate to 9600 To init proceed as follows connect the device over RS485 to a PC with ModComTool config tool set INIT to ON apply power use only the connector without bottom find the controller in the tool Scan set INIT to OFF in the ModComTool tool open the controller window click the Init button in the tool remove and apply power Installation U...

Page 4: ...ot at the top nor bottom Settings Temperature correction Push the right button to increase setpoint push the left button to decrease setpoint The maximum correction range can be modified over the bus e g with the ModComTool configuration tool Sunblind controls Push the up down button shortly to change the slat angle Hold the up down button 1 5 s to travel the sunblind up down Push the down up butt...

Page 5: ...s to select another weekday After all desired events have been edited long push the central button to leave the time schedule settings The controller goes to the basic display mode also after 30 secs of user inactivity Change of setpoints and controller time Switch to the settings mode with a superlong central button push 2 5 s The controller switches to settings mode flashing thermometer icon Pus...

Page 6: ...tarting power of the controller and valve of ca 7 VA and acceptable voltage drop of max 15 the maximum cable length for 10 controllers is about 50 m If the controllers and valves are at higher distance than 50 m from the transformer or more valves are connected to the transformer max 2 valves per controller it is more suitable to supply the controllers locally The RS485 bus is galvanically separat...

Page 7: ...s All dimensions in mm RoHS notice The device contains a non rechargeable battery which backups the real time clock and part of the memory After the device is not operable please return it to the manufacturer or dispose of it in compliance with local regulations ...

Page 8: ...es domat US100 Changes in version 09 2016 Changed the format and reference to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours 05 2018 Change technical data ...