background image

 

domat US100 

05/2018 Subject to technical changes.. 

Terminals 

1

2

3

4

5

6

7

8

9

 

 
 

Terminals as seen from above in the 
bottom part: 
 
1: DI1   presence / window contact input 
2: DO1   heating valve output 
3: DO2   blinds up output 
4: DO3   blinds down output 
5: G0   power, input, outputs 

 

reference point 
6: G0   power, input, outputs 

 

reference point 
7: G 

 power 

 
8: K- 

 communication RS485 - 

9: K+   communication RS485 + 
 

Motor 
connection 
 

Note  that  the  triac  outputs  must  not  be  connected  directly  to  the  sunblind  control 
motor. They are low-power, low-voltage outputs. Consult the sunblind power control 
unit manual if you want to connect US100 to the sunblind control unit. Use 

ME200

, the 

relay power module, to control the sunblind motors directly. 
 

DIP switches 
 

 

 

 

Back of the PCB 
 

BUS END:

 if ON, the bus is terminated (if 

last device on the line) 
 

USR:

 

   not used, reserved for future 

applications 
 

INIT: 

sets the controller into default 

state and sets bus address to 1, baud rate 
to 9600. To init, proceed as follows: 
- connect the device over RS485 to a PC 
with ModComTool config tool 
- set INIT to ON 
- apply power (use only the connector 
without bottom) 
- find the controller in the tool (Scan) 
- set INIT to OFF 
- in the 

ModComTool

 tool, open the 

controller window 
- click the Init button in the tool 
- remove and apply power. 
 

Installation 
  
 

Units  are  intended  for  operating  in  a  normal  and  chemically  non-aggressive 
environment. They do not need any servicing or maintenance. Install them in a vertical 
position at places where they can be operated easily and measure correct values of 
temperature, i.e. in the height of about 150 cm, with no direct sunlight or other heat / 
cool source (AHU outlets, refridgerator, electrical appliances). The device consists of 
two parts: bottom with screw terminal block and cover containing PCB, display, and the 
knob. The bottom part is fixed by 2 or 4 screws to any flat surface or a flush-mounting 

box Ø 50 mm. At the back of the bottom there is an aperture for cabling. The bottom 

Summary of Contents for US100

Page 1: ...l button The room temperature is measured in the range of 20 to 50 C Measured and set values are processed in a PI algorithm at the output of which there is a PWM controlled triac All values are displayed on a large LCD display The output works either as PWM controlled by a PI controller or on off thermostat The functionality and control parameters i e P and I constants and hysteresis can be set w...

Page 2: ...essing and communication examples The communication bus is Modbus RTU over RS485 therefore the controllers are easily to integrate into any SCADA or BMS system Technical data Power 24 V AC 10 Consumption 1 5 W peripherials ca 5VA Measuring range 20 50 C Protection IP20 Sensor accuracy according to DIN IEC 751 Class B Output heating 1x solid state relay zero switching for AC load 24 V AC against G0...

Page 3: ...ller into default state and sets bus address to 1 baud rate to 9600 To init proceed as follows connect the device over RS485 to a PC with ModComTool config tool set INIT to ON apply power use only the connector without bottom find the controller in the tool Scan set INIT to OFF in the ModComTool tool open the controller window click the Init button in the tool remove and apply power Installation U...

Page 4: ...ot at the top nor bottom Settings Temperature correction Push the right button to increase setpoint push the left button to decrease setpoint The maximum correction range can be modified over the bus e g with the ModComTool configuration tool Sunblind controls Push the up down button shortly to change the slat angle Hold the up down button 1 5 s to travel the sunblind up down Push the down up butt...

Page 5: ...s to select another weekday After all desired events have been edited long push the central button to leave the time schedule settings The controller goes to the basic display mode also after 30 secs of user inactivity Change of setpoints and controller time Switch to the settings mode with a superlong central button push 2 5 s The controller switches to settings mode flashing thermometer icon Pus...

Page 6: ...tarting power of the controller and valve of ca 7 VA and acceptable voltage drop of max 15 the maximum cable length for 10 controllers is about 50 m If the controllers and valves are at higher distance than 50 m from the transformer or more valves are connected to the transformer max 2 valves per controller it is more suitable to supply the controllers locally The RS485 bus is galvanically separat...

Page 7: ...s All dimensions in mm RoHS notice The device contains a non rechargeable battery which backups the real time clock and part of the memory After the device is not operable please return it to the manufacturer or dispose of it in compliance with local regulations ...

Page 8: ...es domat US100 Changes in version 09 2016 Changed the format and reference to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours 05 2018 Change technical data ...

Reviews: