domat US100 

Connection

 

 

 

Connection of power, communication, motors, and valve. Suitable cable types for low 
-voltage  installations  are  LAM  DATAPAR  2x0.8  (cross-section  in  mm

2

),  JYTY  2x1 

(diameter in mm) etc. If communication and power are in the same cable, use 4-core 
LAM DATAPAR 2x2x0.8, JYTY 4x1. Up to 100-120 meters, parallel lines of 24 V and data 
bus are no problem. Regarding to EMC it is better if the pairs are twisted, such as with 
the LAM DATAPAR or Belden 8205 cable. 
 
A terminal is designed for maximum 3 wires of 0.8 mm

2

. With cable types as above, 

maximum  (starting)  power  of  the  controller  and  valve  of  ca.  7  VA  and  acceptable 
voltage drop of max. 15 %,  the maximum cable length for 10 controllers is about 50 m.  
 
If the controllers and valves are at higher distance than 50 m from the transformer or 
more valves are connected to the transformer (max. 2 valves per controller), it is more 
suitable to supply the controllers locally. The RS485 bus is galvanically separated and 
connects all controllers, regardless of the way they are powered. 

 

Temperature  
compensation  

After  switching the  unit  on, allow  about  90 mins to  dissipate  the  heat inside  of the 
housing. Then the sensor is measuring correctly. Do not change the sensor correction 
variable immediately after powering the device on! 
 

1
2
3
4
5
6
7

8
9

24 V ~

US100

RS 485 

G0

IN2

IN1

NO1

NC1

COM1

NO2

NC2

COM2

ME200

Summary of Contents for US100

Page 1: ...l button The room temperature is measured in the range of 20 to 50 C Measured and set values are processed in a PI algorithm at the output of which there is a PWM controlled triac All values are displayed on a large LCD display The output works either as PWM controlled by a PI controller or on off thermostat The functionality and control parameters i e P and I constants and hysteresis can be set w...

Page 2: ...essing and communication examples The communication bus is Modbus RTU over RS485 therefore the controllers are easily to integrate into any SCADA or BMS system Technical data Power 24 V AC 10 Consumption 1 5 W peripherials ca 5VA Measuring range 20 50 C Protection IP20 Sensor accuracy according to DIN IEC 751 Class B Output heating 1x solid state relay zero switching for AC load 24 V AC against G0...

Page 3: ...ller into default state and sets bus address to 1 baud rate to 9600 To init proceed as follows connect the device over RS485 to a PC with ModComTool config tool set INIT to ON apply power use only the connector without bottom find the controller in the tool Scan set INIT to OFF in the ModComTool tool open the controller window click the Init button in the tool remove and apply power Installation U...

Page 4: ...ot at the top nor bottom Settings Temperature correction Push the right button to increase setpoint push the left button to decrease setpoint The maximum correction range can be modified over the bus e g with the ModComTool configuration tool Sunblind controls Push the up down button shortly to change the slat angle Hold the up down button 1 5 s to travel the sunblind up down Push the down up butt...

Page 5: ...s to select another weekday After all desired events have been edited long push the central button to leave the time schedule settings The controller goes to the basic display mode also after 30 secs of user inactivity Change of setpoints and controller time Switch to the settings mode with a superlong central button push 2 5 s The controller switches to settings mode flashing thermometer icon Pus...

Page 6: ...tarting power of the controller and valve of ca 7 VA and acceptable voltage drop of max 15 the maximum cable length for 10 controllers is about 50 m If the controllers and valves are at higher distance than 50 m from the transformer or more valves are connected to the transformer max 2 valves per controller it is more suitable to supply the controllers locally The RS485 bus is galvanically separat...

Page 7: ...s All dimensions in mm RoHS notice The device contains a non rechargeable battery which backups the real time clock and part of the memory After the device is not operable please return it to the manufacturer or dispose of it in compliance with local regulations ...

Page 8: ...es domat US100 Changes in version 09 2016 Changed the format and reference to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours 05 2018 Change technical data ...

Reviews: