domat UX0..
05/2018 Subject to technical changes.
1
UX0…
Communicative room units
with sunblind control
Summary
The UX... room unit range is a family of universal communicative human-machine
interface for control of HVAC units and plants, IRC controllers, and blinds. The
units communicate over Modbus RTU / RS485 and they can be used as open
system components with majority of building control system and controllers.
Application
▪
rooms with heating / air conditioning and sunblinds.
▪
systems with fancoils, convectors, floor and radiator heating, AHUs, air
conditioning units.
▪
control of boilers, DHW, heating circuits, building controls in general
▪
monitoring of room temperature and humidity
▪
with a SCADA system: temperature, humidity and status recording,
remote control.
Function
The units acquire temperature and optionally relative humidity in room, temperature
correction (left / right button), sunblind correction (up / down button) and required
operation status (central button or in the menu). In the configurable menu following
values can be set and displayed:
–
temperature, actual temperature correction
–
humidity (actual value only at room units containing the humidity sensor)
–
time (only display at room units with RTC)
–
basic setpoint - day
–
basic setpoint - night
–
outside temperature for heating enable
–
DHW temperature
–
heating curve type (1...4)
–
operation mode (Residential with Day, Night, Time schedule, Off, or Hotel /
Office with Comfort, Standby, Party, Off)
–
fan stage (Auto, Off, St.1, St. 2, St. 3)