On the positive line (35 mm
2
) (see circuit diagram fig.
f
, page 11, fig.
g
,
page 11 and supplementary sheet) of the electrical compressor measure the
power consumption with a current clamp. The measured value should corre-
spond to the table below:
12
Disposal
M
If you wish to scrap the product, ask your local recycling center or specialist
dealer for details about how to do this in accordance with the applicable dis-
posal regulations.
Outside temperature
High pressure
Compressor power
consumption at
maximum speed
Approx. 15 °C
Approx. 7 bar
Approx. 60 A
Approx. 20 °C
Approx. 9 bar
Approx. 70 A
Approx. 25 °C
Approx. 10 bar
Approx. 80 A
Approx. 30 °C
Approx. 12 bar
Approx. 95 A
Approx. 35 °C
Approx. 14 bar
Approx. 105 A