Troubleshooting
CRX
34
Compressor does not run (battery connection)
3
The motor doesn't start
The rotor is jammed.
The pressure difference in the cooling system
is too high (> 5 bar).
4
Speed too low
If the cooling system is overloaded, the mini-
mum speed of the motor of 1,850 rpm can-
not be maintained.
5
Overheating of the elec-
tronics unit
If the cooling system is loaded too heavily or
the temperature is set too high, the electron-
ics can overheat.
Constantly
Temperature sensor
errors
Temperature sensor is defective.
Problem
Possible cause
Remedy
U
Term
= 0 V
There is an interruption in the
battery – electronics connection
Establish a connection
Main switch faulty (if installed)
Replace the main switch
Additional supply line fuse has blown
(if installed)
Replace the supply line
fuse
U
Term
≤
U
ON
Battery voltage is too low
Charge the battery
Start attempt with
U
Term
≤
U
OFF
Loose cables
Poor contact (corrosion)
Establish a connection
Battery capacity too low
Replacing the battery
Cable cross section too small
Replace the cable
(fig.
Start attempt with
U
Term
≥
U
ON
Ambient temperature too high
–
Insufficient ventilation
Move the refrigerator to
another location
Condenser is dirty
Clean the condenser
Electric circuit between
the pins in the compres-
sor interrupted
Defective compressor
Contact customer service
Number of
flashes
Fault
Possible cause
CRX50-65-80-110-140-IO-US.book Seite 34 Mittwoch, 15. Juli 2020 10:16 10
Summary of Contents for 9105305962
Page 8: ...CRX 8 2 1 9 1 2 0 CRX50 65 80 110 140 IO US book Seite 8 Mittwoch 15 Juli 2020 10 16 10 ...
Page 9: ...CRX 9 a b c CRX50 65 80 110 140 IO US book Seite 9 Mittwoch 15 Juli 2020 10 16 10 ...
Page 11: ...CRX 11 1 rd bk f 1 2 g CRX50 65 80 110 140 IO US book Seite 11 Mittwoch 15 Juli 2020 10 16 10 ...
Page 91: ...CRX50 65 80 110 140 IO US book Seite 91 Mittwoch 15 Juli 2020 10 16 10 ...