Troubleshooting
CRX1050, CRX1065, CRX1080
28
Compressor does not run (battery connection)
Fault
Possible cause
Remedy
U
Term
= 0 V
The connection between the battery
and electronics unit has been inter-
rupted.
Establish a connection
Main switch faulty (if installed)
Replace the main switch
Additional supply line fuse has blown
(if installed)
Replace the supply line
fuse
U
KL
≤
U
ON
Battery voltage is too low
Charge the battery
Start attempt with
U
Term
≤
U
OFF
Loose cables
Poor contact (corrosion)
Establish a connection
Battery capacity too low
Replacing the battery
Cable cross section too small
Replace the cable
(fig.
a
, page 7)
Start attempt with
U
Term
≥
U
ON
Ambient temperature too high
–
Insufficient ventilation
Move the refrigerator to a
different position
Condenser is dirty
Clean the condenser
Electric circuit between
the pins in the compres-
sor interrupted
Defective compressor
Replace the compressor
U
Term
Voltage between the positive and negative terminals of the electronics
U
ON
Cut-in voltage of the electronics
U
OFF
Cut-off voltage of the electronics
Summary of Contents for CRX 1050
Page 2: ......
Page 3: ...CRX1050 CRX1065 CRX1080 3 CRX 1050 1 2 3 5 4 6 7 1 1 2 3 5 4 6 7 CRX 1065 2...
Page 4: ...CRX1050 CRX1065 CRX1080 4 1 2 3 5 4 6 7 CRX 1080 3 1 2 3 4 6 5 7 8 4...
Page 5: ...CRX1050 CRX1065 CRX1080 5 1 4 3 2 ca 50 mm 5 2 1 6...
Page 6: ...CRX1050 CRX1065 CRX1080 6 1 2 7 8...
Page 8: ...CRX1050 CRX1065 CRX1080 8 1 rt sw b 2 3 1 c 1 Vent Lock d...
Page 9: ...CRX1050 CRX1065 CRX1080 9 380 534 500 CRX 1050 e CRX 1065 448 525 545 f CRX 1080 475 640 528 g...
Page 121: ......
Page 122: ......
Page 123: ......