Self-Contained Air Conditioning System
Intended Use
3 Intended Use
This manual is intended for the installation of Turbo,
Vector Compact, EnviroCool, and Low Profile self-
contained air conditioning systems. Improper installation
procedures can result in unsatisfactory performance
or premature failure of these air conditioning units.
Installation can typically be performed by one person,
with brief help from an additional person.
The manufacturer accepts no liability for damage in the
following cases:
• Faulty assembly or connection
• Damage to the product resulting from mechanical
influences and excess voltage
• Alterations to the product without express permission
from the manufacturer
• Use for purposes other than those described in the
operating manual
Dometic Corporation reserves the right to modify
appearances and specifications without notice.
4 Specifications
This section contains specification data for the self-
contained air conditioning system.
Minimum Duct and Grille Sizes per BTU Capacity
3 .5 k BTU 6 k BTU 8 k BTU 10 k BTU
12 k BTU 16 k BTU 18 k BTU 27 k BTU
Minimum Duct Diameter
[in . (mm)]
3.0 (76)
4.0 (102) 5.0 (127) 6.0 (152)
6.0 (152) 7.0 (178)
7.0 (178)
8.0 (203)
Minimum Duct Area
[sq . in . (sq . cm)]
6.8 (44)
12.6 (81) 19.6
(126)
28.3 (183)
28.3
(183)
38.5
(248)
38.5
(248)
50.3
(325)
Minimum Return Air Grille
[sq . in . (sq . cm)]
64.0 (413) 64.0
(413)
80.0
(516)
100.0
(645)
130.0
(839)
200.0
(1290)
200.0
(1290)
240.0
(1548)
Minimum Supply Air Grille
[sq . in . (sq . cm)]
12.0 (77)
32.0
(206)
48.0
(310)
60.0 (387) 70.0
(452)
80.0
(516)
100.0
(165)
140.0
(903)
Operating Water Temperature and Pressure
Minimum Operating
Water Temperature
40.0 °F (4 °C)
Maximum Operating
Water Temperature
80.0 °F (27 °C)
Minimum Operating
Water Pressure
4.2 psi (29 kPa)
Maximum Operating
Water Pressure
6.0 psi (41.4 kPa)
I
The unit can operate outside these conditions with
reduced capacity.
5 Pre-Installation
NOTICE:
Failure to obey these notices could result in
damage to the product:
• The Turbo self-contained condensate base pan is
equipped with vibration isolators installed in the
bottom of the pan. These isolators are designed to
dampen the vibration caused by the operating air
conditioning unit from transferring into the mounted
surface. Care must be taken when moving the
air conditioning unit across mounting surfaces as
isolators can be damaged.
• Clean the air filter regularly according to the
instructions in the owner’s control manual to ensure
proper operation.