EN
29
5 Troubleshooting
In the unlikely event that a problem occurs on the equipment, this troubleshooting guide can be used to identify the probable cause and remedy.
Troubleshooting should only be attempted by competent personnel. All major repair, and calibration work should be
undertaken by a domnick hunter trained, qualified and approved engineer.
Fault Probable
Cause
Remedy
Fuse Blown
Replace Fuse
Ribbon cable disconnected
Reconnect Ribbon cable
Power Connected but LCD and status
indicators not illuminated.
Power disconnected
Reconnect Power
Service Overdue
Service the generator
Internal gas leak
Check and Rectify
External gas leak
Check and Rectify
No / Low gas outlet pressure
Low inlet pressure
Ensure pressure meets required
specification
Defective Oxygen cell.
Replace.
High Oxygen concentration.
Leak in system piping.
Check and Rectify
Compressor or ring main pressure low.
Check and Rectify
Inlet valve not open
Check and Rectify
Low inlet pressure
Defect on pre-treatment package.
Refer to pre-treatment manual.
Silencer loose or defective.
Check and Rectify
Excessive noise or vibration
Solenoid valve wear or coil loose.
Check and replace if required.
High outlet pressure.
Outlet regulator defective.
Reset or replace.
Summary of Contents for Maxigas 104
Page 1: ...104 120 SERVICE GUIDE ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ...10 Menu Map ...
Page 11: ...11 ...
Page 14: ......
Page 30: ......
Page 32: ......
Page 33: ...EN 33 APPENDIX A SCHEMATICS ...
Page 34: ......
Page 35: ......